Table 33: The technical data of the Vacon
®
100 FLOW AC drive
Technical item or function
Technical data
Ambient conditions
Vibration:
EN61800-5-1
EN60068-2-6
5-150 Hz
Displacement amplitude 0.5 mm (peak) at 5-22 Hz
Maximum acceleration amplitude 1 G at 22-150 Hz
Shock:
EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: maximum 15 G, 11 ms (in pack-
age)
Enclosure class
IP21: standard
IP54: option
EMC (at default settings)
Immunity
Fulfils EN61800-3, 1
st
and 2
nd
environment
Emissions
•
380-500 V: EN 61800-3 (2004), category C3, if the
drive is correctly installed.
•
525-690 V: EN 61800-3 (2004), category C3, if the
drive is correctly installed.
•
All: The drive can be changed to C4 for IT type
mains. See chapter 7.5 Installation in an IT system.
Noise level
Average noise level (min-
max) sound pressure
level in dB(A)
The sound pressure depends on the cooling fan speed,
which is controlled in accordance with the drive tem-
perature.
MR8: 58-73
MR9: 54-75
MR10/MR12: 58-75
Safety
EN 61800-5-1, CE (See the nameplate of the drive for
more approvals.)
TECHNICAL DATA, VACON® 100 FLOW
VACON · 109
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
9