8.2
VACON
®
100 - TECHNICAL DATA
Table 30: The technical data of the Vacon
®
100 AC drive
Technical item or function
Technical data
Mains connection
Input voltage U
in
380-500 V, 525-690 V, -10%...+10%
Input frequency
50-60 Hz, -5...+10%
Connection to mains
Once per minute or less frequently
Starting delay
8 s (MR8 to MR12)
Mains
•
Mains types: TN, TT, and IT
•
Short circuit current: the maximum short circuit
current must be < Icc 65 kA.
Motor connection
Output voltage
0-U
in
Continuous output current
I
L
: Ambient temperature max. +40 °C overload 1.1 x I
L
(1 min/10 min)
I
H
: Ambient temperature max. +40 °C overload 1.5 x I
H
(1 min/10 min)
I
H
in 690 V drives: Ambient temperature max. +40 °C
overload 1.5 x I
H
(1 min/10 min)
Output frequency
0-320 Hz (standard)
Frequency resolution
0.01 Hz
TECHNICAL DATA, VACON® 100