The requirements: +CAPU Auxiliary AC supply terminals or +CAPT Auxiliary voltage
transformer
N
L
1
1/
N
/P
E
-XD1
-XD1
-FCC
2 A
-XD10
-PE
Fig. 14: The AC customer socket
+CDLP: SIGNAL LIGHTS AND RESET BUTTON
This option includes signal lights on the control compartment door for Ready, Run and Fault
states of the AC drive. The door also has a button for the reset function of the AC drive. The
Ready signal light is not available if you use the option board OPT-F4.
The requirements:
•
+CAPD 24 VDC power supply
•
+CAPU Auxiliary AC supply terminals or +CAPT Auxiliary voltage transformer
+CTID: EXTENDED I/O TERMINALS
The option includes 20 control terminals (-XDW) in the control compartment for your own
free use.
No requirements.
+CAPU: AUXILIARY AC SUPPLY TERMINALS
This option provides terminals –XD1.1 for an external voltage supply. The external supply
must be short-circuit protected. The power of this supply depends on other selected cabinet
options.
The requirements: Not +CAPT Auxiliary voltage transformer.
WARNING!
The main switch does not disconnect the external voltage supply. Before you touch
the components of the control compartment, disconnect the external voltage
supply. The voltage can be very dangerous.
2
-FC6
-XD1.1
-XD1
10 A
Fig. 15: The auxiliary AC supply terminals
+CPS0: STO WITH EMERGENCY STOP PUSH BUTTON ON DOOR
This option provides the STO (Safe Torque Off) function with the OPT-BJ option board and an
emergency stop push button on the door of the control compartment. The STO Channel 1 and
MOUNTING
VACON · 27
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
4
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives installation manual enclosed drives ...
Page 2: ......
Page 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...