Table 13: The recommended cables and terminal lugs in 380-500 V (NAM)
Frame
Type
I
L
(A)
Mains and motor
cable (Cu) [AWG/
kcmil]
Mains and motor
cable
termination,
Panduit terminal
part number
Grounding
terminal, bolt and
lug size
MR8
0140 5
140
(3x2/0+3x10)
LCAX2/0-38-X
P10-56R-L
0170 5
170
(3x4/0+3x8)
LCAX4/0-38-X
LCAX8-56-L
0205 5
205
(3x262+3x6)
LCAX250-38-X
LCAX6-56-L
MR9
0261 5
261
2x(3x2/0+3x10)
LCAX2/0-38-X
P10-56R-L
0310 5
310
2x(3x4/0+3x8)
LCAX4/0-38-X
LCAX8-56-L
MR10
0385 5
385
2x(3x262+3x6)
LCAX250-12-X
LCAX6-56-L
0460 5
460
2x(3x313+3x6)
LCAX300-12-6
LCAX6-56-L
0520 5
520
2x(3x373+3x6)
LCAX350-12-6
LCAX6-56-L
0590 5
590
3x(3x262+3x6)
LCAX250-12-X
LCAX6-56-L
MR12
0650 5
650
4x(3x4/0+3x8)
LCAX4/0-12-X
LCAX8-56-L
0730 5
730
4x(3x4/0+3x8)
LCAX4/0-12-X
LCAX8-56-L
0820 5
820
4x(3x262+3x6)
LCAX250-12-X
LCAX6-56-L
0920 5
920
4x(3x313+3x6)
LCAX300-12-6
LCAX6-56-L
1040 5
1040
4x(3x373+3x6)
LCAX350-12-6
LCAX6-56-L
1180 5
1180
6x(3x262+3x6)
LCAX250-12-X
LCAX6-56-L