Table 33: The technical data of the Vacon
®
100 FLOW AC drive
Technical item or function
Technical data
Protections
Overvoltage trip limit
Mains voltage 500 V: 911 VDC
Mains voltage 690 V: 1258 VDC
Undervoltage trip limit
Depends on mains voltage (0.8775 x mains voltage):
Mains voltage 400 V: trip limit 351 VDC
Mains voltage 500 V: trip limit 438 VDC
Mains voltage 525 V: trip limit 461 VDC
Mains voltage 690 V: trip limit 606 VDC
Earth fault protection
Yes
Mains supervision
Yes
Motor phase supervision
Yes
Overcurrent protection
Yes
Unit overtemperature
protection
Yes
Motor overload protection Yes. The motor overload protection activates at 110%
of the full load current.
Motor stall protection
Yes
Motor underload protec-
tion
Yes
Short-circuit protection of
+24 V and +10 V reference
voltages
Yes
VACON · 110
TECHNICAL DATA, VACON® 100 FLOW
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205