Table 11: Drive fuses, 380-500 V, Bussmann (IEC)
Frame
Type
I
L
[A]
Catalogue number of the
fuse
Fuse
rating
[A]
Number
of fuses
needed
Fuse
size
Minimum
prospective
short
circuit
current [A]
MR8
0140 5
140
170M3817D
315
3
1
1700
0170 5
170
170M3818D
350
3
1
1950
0205 5
205
170M3819D
400
3
1
2400
MR9
0261 5
261
170M5810D
500
3
2
2800
0310 5
310
170M5812D
630
3
2
4000
MR10
0385 5
385
170M5814D
800
3
2
5750
0460 5
460
170M6814D
1000
3
3
7500
0520 5
520
170M6892D
1100
3
3
8500
0590 5
590
170M8554D
1250
3
3
10500
MR12
0650 5
650
170M5814D
800
6
2
5750
0730 5
730
170M5814D
800
6
2
5750
0820 5
820
170M6813D
900
6
3
6000
0920 5
920
170M6814D
1000
6
3
7500
1040 5
1040
170M6892D
1100
6
3
8500
1180 5
1180
170M8554D
1250
6
3
10500
POWER CABLING