Table 26: The recommended brake resistor types and the calculated resistance of the drive,
380-500 V
Frame
Duty cycle
Type of brake resistor
Resistance [Ω]
MR8
Light duty
BRR 0105 LD 5
6.5
Heavy duty
BRR 0105 HD 5
6.5
MR9
Light duty
BRR 0300 LD 5
3.3
Heavy duty
BRR 0300 HD 5
3.3
MR10
Light duty
BRR 0520 LD 5
1.4
Heavy duty
BRR 0520 HD 5
1.4
MR12
Light duty
BRR 0520 LD 5
2 x 1.4
Heavy duty
BRR 0520 LD 5
2 x 1.4
Table 27: The recommended brake resistor types and the calculated resistance of the drive,
525-690 V
Frame
Drive type
Duty cycle
Type of brake
resistor
Resistance [Ω]
MR8
0080
Light duty
BRR 0052 LD 6
18
Heavy duty
BRR 0052 HD 6
18
0100-0125
Light duty
BRR 0100 LD 6
9
Heavy duty
BRR 0100 HD 6
9
MR9
0144
Light duty
BRR 0100 LD 6
9
Heavy duty
BRR 0100 HD 6
9
0170-0208
Light duty
BRR 0208 LD 6
7
Heavy duty
BRR 0208 HD 6
7
MR10
0261-0416
Light duty
BRR 0416 LD 6
2.5
Heavy duty
BRR 0416 HD 6
2.5
MR12
0460-0820
Light duty
BRR 0416 LD 6
2 x 2.5
Heavy duty
BRR 0416 HD 6
2 x 2.5
The frame MR12 includes 2 power units, each of which has a brake chopper. The brake
choppers must have their own brake resistors. See Fig. 27 The inside layout of MR12, without
protective covers.
VACON · 96
TECHNICAL DATA, VACON® 100
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives installation manual enclosed drives ...
Page 2: ......
Page 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Page 115: ......