5.3
PREPARING FOR THE CABLE INSTALLATION
•
Before you start, make sure that none of the components of the AC drive is live. Read
carefully the warnings in chapter 2 Safety.
•
Make sure that the motor cables are sufficiently far from other cables.
•
The motor cables must cross other cables at an angle of 90°.
•
If it is possible, do not put the motor cables in long parallel lines with other cables.
L1 L2 L3 U V W
B
A
C
E
F
G
D
A. The mains cables
B. The motor cables
C. The grounding conductor
D. Pull relief
E. The grounding clamp for cable shield,
360° grounding
F. The control cable
G. The grounding bar of the control cable
•
Only use symmetrically EMC shielded mains and motor cables.
•
The maximum length of shielded motor cables is 200 m (MR8-MR12).
•
If the cable insulation checks are necessary, see chapter 7.3 Measuring the cable and
motor insulation for instructions.
•
If the motor cables are in parallel with other cables, obey the minimum distances.
•
The distances are also valid between the motor cables and the signal cables of other
systems.
Table 19: The minimum distances between cables
The distance between cables
[m]
The length of the shielded cable
[m]
0.3
≤ 50
1.0
≤ 200
VACON · 50
POWER CABLING
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205