7.2
OPERATION OF THE MOTOR
7.2.1
CHECKS BEFORE STARTING THE MOTOR
Before you start the motor, do these checks.
•
Make sure that all the START and STOP switches that are connected to the control
terminals are in the STOP position.
•
Make sure that you can start the motor safely.
•
Activate the Start-up wizard. See the Application Manual for the AC drive that you have.
•
Set the maximum frequency reference (that is, the maximum speed of the motor), so
that it agrees with the motor and the device that is connected to the motor.
7.3
MEASURING THE CABLE AND MOTOR INSULATION
Do these checks if necessary.
The insulation checks of the motor cable
1
.
Disconnect the motor cable from the terminals U, V, and W and from the motor.
2
.
Measure the insulation resistance of the motor cable between phase conductors 1 and 2,
between phase conductors 1 and 3, and between phase conductors 2 and 3.
3
.
Measure the insulation resistance between each phase conductor and the grounding
conductor.
4
.
The insulation resistance must be >1 MΩ at the ambient temperature of 20 °C (68 °F).
The insulation checks of the mains cable
1
.
Disconnect the mains cable from the terminals L1, L2, and L3 and from mains.
2
.
Measure the insulation resistance of the mains cable between phase conductors 1 and 2,
between phase conductors 1 and 3, and between phase conductors 2 and 3.
3
.
Measure the insulation resistance between each phase conductor and the grounding
conductor.
4
.
The insulation resistance must be >1 MΩ at the ambient temperature of 20 °C (68 °F).
The insulation checks of the motor
1
.
Disconnect the motor cable from the motor.
2
.
Open the bridging connections in the motor connection box.
3
.
Measure the insulation resistance of each motor winding. The voltage must be the same
or higher than the motor nominal voltage, but not higher than 1000 V.
4
.
The insulation resistance must be >1 MΩ at the ambient temperature of 20 °C (68 °F).
5
.
Obey the instructions of the motor manufacturer.
7.4
INSTALLATION IN A MARINE ENVIRONMENT
When you install the AC drive in a marine environment, see the Marine Installation Guide.
7.5
INSTALLATION IN AN IT SYSTEM
If your mains is impedance-grounded (IT), the AC drive must have the EMC protection level
C4. If your drive has the EMC protection level C3, it is necessary to change it to C4. To do this,
remove the EMC jumper.
COMMISSIONING AND ADDITIONAL INSTRUCTIONS
VACON · 69
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
7
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives installation manual enclosed drives ...
Page 2: ......
Page 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Page 115: ......