10 In MR8 and MR9, remove the external 24 VDC
power supply wires from the terminals. (Unless the
control unit of the drive is normally supplied with
an external 24 VDC supply.)
11 In MR10 and MR12, remove the external 24 VDC
wires from the X50 connector of the measurement
board. In MR12, there are two X50 connectors.
12 In MR10 and MR12, attach the service lid. In MR12,
there are two service lids.
13 After the downloading procedure is complete, start
the Startup wizard (see the Application Manual).
WARNING!
Before you connect the drive to mains, make sure that the front cover and the cable
cover of the drive are closed. The connections of the AC drive are live when the
drive is connected to mains.
COMMISSIONING AND ADDITIONAL INSTRUCTIONS
VACON · 93
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
7