75
6
F
2
S
0
8
5
0
Setting
The setting elements necessary for the PSB and their setting ranges are as shown in the table
below.
Element Range
Step
Default Remarks
PSBSZ
0.50 - 15.00
Ω
0.01
Ω
2.00
Ω
PSBS detection zone
( 2.5 - 75.0
Ω
0.1
Ω
10.0
Ω
) (*)
PSBGZ
0.50 - 15.00
Ω
0.01
Ω
2.00
Ω
PSBG detection zone
( 2.5 - 75.0
Ω
0.1
Ω
10.0
Ω
) (*)
EFL
0.5 - 5.0 A
0.1 A
1.0 A
Residual overcurrent
( 0.10 - 1.00 A
0.01 A
0.20 A)
TPSB
20 - 60
1 ms
40 ms
Power swing timer
PSB-Z1
OFF/ON
ON
Z1 blocked under power swing
PSB-Z2
OFF/ON
ON
Z2 blocked under power swing
PSB-Z3
OFF/ON
OFF
Z3 blocked under power swing
PSB-CR OFF/ON
ON
Carrier
trip blocked under power swing
PSB-ZR
OFF/ON
OFF
ZR blocked under power swing
(*) Values shown in the parentheses are in the case of 1A rating. Other values are in the case of 5A
rating.
Residual overcurrent element EFL is used in common with the following functions.
•
VT failure detection
•
Earth fault distance protection
The PSBIN reach is set automatically to coordinate with the Z3 and Z4 settings.
Note: In the case of the quadrilateral characteristic, if the ZR reach is larger than the Z4, the PEB-IN
reach depends on the ZR reach. Therefore, the ZR must be set less than the Z4 whether the ZR
used or not.
The right side forward and reverse blinders for PSBIN are shared with the right side forward and
reverse blinders of the distance protection characteristic, BFRS/BFRG and BRRS/BRRG
respectively, ensuring that the PSB element coordinates properly with the protection, for both mho
and quadrilateral characteristics.
The positive reactive reach setting is fixed so that the setting makes the reactance element
tangential to the Z3 distance element when the Z3 is mho-based or takes the same value as the Z3
reactive reach setting when the Z3 is quadrilateral-based.
The negative resistive reach takes the same value as that of the positive reach. The negative
reactive reach setting is fixed so that the setting makes the reactance element tangential to the Z4
distance element when the Z4 is mho-based or takes the same value as the Z4 reactive reach setting
when the Z4 is quadrilateral-based.
PSBOUT encloses PSBIN and the margin between the two is determined by the user-settable
power swing detection zone width, PSBSZ and PSBGZ, for phase and earth fault characteristics
respectively.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...