List of Information
IEC103 Configurator Default setting
INF
Description
Contents
GI Type
COT
FUN
DPI
ID
Signal No.
OFF ON
Standard Information numbers in monitor direction
System Function
0 End of General Interrogation
Transmission completion of GI items.
--
8
10
255
--
--
--
0 Time Synchronization
Time Synchronization ACK.
--
6
8
255
--
--
--
2 Reset FCB
Reset FCB(toggle bit) ACK
--
5
3
192
--
--
--
3 Reset CU
Reset CU ACK
--
5
4
192
--
--
--
4 Start/Restart
Relay start/restart
--
5
5
192
--
--
--
5 Power On
Relay power on.
Not supported
--
--
--
Status Indications
16 Auto-recloser active
If it is possible to use auto-recloser, this item is set
active, if impossible, inactive.
GI
1
1, 9, 11, 12
192
1411
1
2
17 Teleprotection active
If protection using telecommunication is available,
this item is set to active. If not, set to inactive.
GI
1
1, 9, 12
192
1412
1
2
18 Protection active
If the protection is available, this item is set to
active. If not, set to inactive.
GI
1
1, 9, 12
192
1413
1
2
19 LED reset
Reset of latched LEDs
--
1
1, 11, 12
192
1409
--
2
20 Monitor direction blocked
Block the 103 transmission from a relay to control
system. IECBLK: "Blocked" settimg.
GI
1
9, 11
192
1241
1
2
21 Test mode
Transmission of testmode situation froma relay to
control system. IECTST "ON" setting.
GI
1
9, 11
192
1242
1
2
22 Local parameter Setting
When a setting change has done at the local, the
event is sent to control system.
Not supported
23 Characteristic1
Setting group 1 active
GI
1
1, 9, 11, 12
192
1243
1
2
24 Characteristic2
Setting group 2 active
GI
1
1, 9, 11, 12
192
1244
1
2
25 Characteristic3
Setting group 3 active
GI
1
1, 9, 11, 12
192
1245
1
2
26 Characteristic4
Setting group 4 active
GI
1
1, 9, 11, 12
192
1246
1
2
27 Auxiliary input1
Binary input 1
No set
28 Auxiliary input2
Binary input 2
No set
29 Auxiliary input3
Binary input 3
No set
30 Auxiliary input4
Binary input 4
No set
Supervision Indications
32 Measurand supervision I
Zero sequence current supervision
GI
1
1, 9
192
1267
1
2
33 Measurand supervision V
Zero sequence voltage supervision
GI
1
1, 9
192
1268
1
2
35 Phase sequence supervision Negative sequence voltage supevision
GI
1
1, 9
192
1269
1
2
36 Trip circuit supervision
Output circuit supervision
Not supported
37 I>>backup operation
Not supported
38 VT fuse failure
VT failure
GI
1
1, 9
192
891
1
2
39 Teleprotection disturbed
CF(Communication system Fail) supervision
GI
1
1, 9
192
226
1
2
46 Group warning
Only alarming
GI
1
1, 9
192
1258
1
2
47 Group alarm
Trip blocking and alarming
GI
1
1, 9
192
1252
1
2
Earth Fault Indications
48 Earth Fault L1
A phase earth fault
No set
49 Earth Fault L2
B phase earth fault
No set
50 Earth Fault L3
C phase earth fault
No set
51 Earth Fault Fwd
Earth fault forward
Not supported
52 Earth Fault Rev
Earth fault reverse
Not supported
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...