Setting depending on communication mode
The setting depending on communication mode is shown in the following table.
Setting A-MODE B-MODE
GPS-MODE
Default
setting
Remarks
Communication
mode
COMMODE Must select “A” of
A/B/GPS
Must select “B” of
A/B/GPS
Must select “GPS”
of A/B/GPS
B
GPS backup
mode
GPSBAK --
--
On/Off
On
MODE2B shifted
automatically
AUTO2B --
--
On/Off
Off
Phase difference
check
SRC
θ
--
--
Disable/I
I
Available for only
2TERM setting
Terminal
application
TERM 2TERM/3TERM/
DUAL
2TERM/3TERM/
DUAL
2TERM/3TERM
2TERM
For 3 terminal
application model
Relay address
monitoring
RYIDSV --
On/Off
On/Off
On
Multi-phase
autoreclosing
Autoreclose
mode
MPAR2/MPAR3 MPAR2/MPAR3 MPAR2/MPAR3 SPAR&TPAR RYIDSV=Off
is
required
Open terminal
detection
OTD On/Off
On/Off
On/Off
Off
Zero-phase
current differential
DIFG On/Off
On/Off
On/Off
On
Out-of-step
tripping
OST Trip/BO/Off Trip/BO/Off Trip/BO/Off Off
Fault locator
FL
On/Off
On/Off
On/Off
On
Remote
differential trip
RDIF
--
On/Off
On/Off
On
Available for 3TERM
application
--: don’t care.
Terminal application
In A-MODE and B-MODE, anyone of 2TERM, 3TERM or DUAL can be selected. In
GPS-MODE, however, DUAL cannot be selected.
Multi-phase autoreclosing
To apply the multi-phase autoreclosing with MPAR2 or MPAR3, the relay address monitoring
RYIDSV in B-MODE and GPS-MODE must be set to “OFF”. When the RYIDSV=OFF, CBLS
(CBDS) condition is sent.
If shared with the relay address monitoring, the bits for CBLS condition can be assigned instead
of the bits for DIFG or OST/FL by PLC function when DIFG or OST/FL is not used.
Automatic open terminal detection OTD
In B-MODE and GPS-MODE, the RYIDSV=OFF setting for relay address monitoring is
required to use the open terminal detection function (OTD=On).
If shared with the relay address monitoring, the following methods can be applied:
(1)
Only one bit with open terminal condition instead of CBLS condition can be sent by
sub-communication bit.
(2)
If DIFG or OST/FL is not used, the bits for CBLS condition can be assigned instead of the
bits for DIFG or OST/FL by PLC function.
The open terminal detection in B-MODE and GPS-MODE do not automatically change
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...