207
6
F
2
S
0
8
5
0
/6 Protection element 1/ **
DIFI1( 0.50- 10.00): 1.00 _ A
DIFI2( 3.0- 120.0): 2.0 A
DIFGI( 0.25- 5.00): 0.50 A
DIFIC( 0.00- 5.00): 1.00 A
Vn ( 100- 120): 110 V
TDIFG( 0.00- 10.00): 0.10 s
DIFSV( 0.05- 1.00): 0.10 A
TIDSV( 0- 60): 10 s
OCBF ( 0.5- 10.0): 0.5 A
TBF1 ( 50- 500): 50 ms
TBF2 ( 50- 500): 50 ms
OC ( 0.5- 100.0): 0.5 A
TOC ( 0.00- 10.00): 1.00 s
OC1 ( 0.5- 100.0): 1.0 A
OCI ( 0.5- 25.0): 0.5 A
TOCI ( 0.05- 1.00): 1.00
TOCIR( 0.0- 10.0): 0.0 s
EF ( 0.5- 5.0): 0.5 A
TEF ( 0.00- 10.00): 1.00 s
EFI ( 0.5- 5.0): 0.5 A
TEFI ( 0.05- 1.00): 1.00
TEFIR( 0.0- 10.0): 0.0 s
THM ( 2.0- 10.0): 5.0 A
THMIP( 0.0- 5.0): 0.0 A
TTHM ( 0.5- 300.0): 10.0 min
THMA ( 50- 99): 80 %
OCCHK( 0.5- 5.0): 0.5 A
HYSθ ( 1- 5): 1 deg
: : :
: : :
TECCB( 0.00-200.00): 0.10 s
TSBCT( 0.00- 1.00): 0.10 s
•
Move the cursor to a setting line.
•
Enter the numerical value.
•
Press
the ENTER key to confirm the entry and the cursor will move to the next line below.
(If a numerical value outside the displayed range is entered, "Error: Out of range" appears on
the top line and the cursor remains on the line. Press the CANCEL key to clear the entry.)
•
After completing the setting on the screen, press the END key to return to the upper screen.
To correct the entered numerical value, do the followings.
•
If it is before pressing the ENTER key, press the CANCEL key and enter the new
numerical value.
•
If it is after pressing the ENTER key, move the cursor to the correct line by pressing the
and keys and enter the new numerical value.
Note:
If the CANCEL key is pressed after any of the entry is confirmed by pressing the ENTER
key, all the entries made so far on the screen concerned are canceled and the screen returns to
the upper one.
To enter a text string
Text strings are entered in the bracket under "Plant name" or "Description" screen.
To select a character, use keys 2, 4, 6 and 8 to move the blinking cursor down, left, up and right.
"
→
" and "
←
" on each of lines 2 to 4 indicate a space and backspace, respectively. A maximum
of 22 characters can be entered within the brackets.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...