Setting
The setting elements necessary for the SOTF protection and their setting ranges are as follows:
Element Range
Step Default Remarks
OCH
2.0 - 15.0 A
0.1 A
6.0 A
Overcurrent setting
( 0.4 - 3.0 A
0.1 A
1.2 A) (*)
TSOTF
0 – 300 s
1 s
5 s
SOTF check timer
SOTF - OC
OFF/ON
ON
Overcurrent tripping
SOTF - Z1
OFF/ON
OFF
Zone 1 tripping
SOTF - Z2
OFF/ON
OFF
Zone 2 tripping
SOTF - Z3
OFF/ON
OFF
Zone 3 tripping
SOTF - R
OFF/ON
OFF
Zone R tripping
SOTF-DL CB/UV/BOTH
CB
SOTF
control
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The OCH element and its setting are common with the stub protection.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...