119
6
F
2
S
0
8
5
0
the scheme switch.
When [VCHK] is set to "SYN", three-phase autoreclose is performed only with the synchronism
check.
When [VCHK] is set to "OFF", three-phase autoreclose is performed without the voltage and
synchronism check.
The voltage and synchronism check requires a single-phase reference voltage from the busbar or
line. If three-phase voltages used by the current differential protection are supplied from the line
voltage transformer, the reference voltage will need to be supplied from the busbar voltage
transformer. On the contrary, if three-phase voltages used by the current differential protection
are supplied from the busbar voltage transformer, the reference voltage will need to be supplied
from the line voltage transformer.
Additionally, it is not necessary to fix the phase of the reference voltage.
To match the busbar voltage and line voltage for the voltage and synchronism check option
described above, the GRL100 has the following three switches as shown in Figure 2.15.2.4:
[VTPSEL]:
This switch is used to match the voltage phases. If the A-phase voltage or
A-phase to B-phase voltage is used as a reference voltage, "A" is selected.
[VT-RATE]: This switch is used to match the magnitude and phase angle. "PH/G" is
selected when the reference voltage is a single-phase voltage while
"PH/PH" is selected when it is a phase-to-phase voltage.
[3PH-VT]:
"Bus" is selected when the three-phase voltages are busbar voltages while
"Line" is selected when they are line voltages.
Vref
Vc
Vb
Va
[VTPSEL]
"C"
"B"
"A"
+
+
+
[VT - RATE]
"PH/G"
[3PH - VT]
"Line"
"Bus"
"PH/PH"
+
+
+
+
Busbar or line
voltages
Line or busbar
reference voltage
Voltage check
&
Synchronism check
Figure 2.15.2.4 Matching of Busbar Voltage and Line Voltage
The signal 3PLL shown in Figure 2.15.2.3 is output when all three phase voltages are live, and it
is available by the [3PH-VT] = LINE setting.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...