1 FWD/REV run select (set value = 00)
• When 0 is set in Sn-15, the mode becomes 3-wire sequence mode.
Fig. 12 3-wire sequence
2 Operation signal select (set value = 01)
• Selection of operation signals is enabled only when the drive is stopped.
Open:
The AC drive operates according to the setting of Sn-04 1st, 2nd digits
and Sn-08 1st, 2nd digits.
Closed:
The AC drive operates by frequency reference and run command from the
digital operator.
<Example 1>
For local/remote mode select, set Sn-04 = × × 00 and Sn-08=× × 11.
Open:
Frequency reference and run command from control circuit terminals are
accepted (Remote mode).
Closed:
Frequency reference and run commands from the digital operator are
accepted (Local mode).
<Example 2>
For local/remote mode select, set Sn-04 = × × 00 and Sn-08=× × 00.
Open:
Frequency reference and run command are input by RS-485 communication
option card (Remote mode). Please refer to Appendix C for a detailed disscussion
of RS485 communications.
Closed:
Frequency reference and run/stop command are input by digital operator
(Local mode)
3 Option card/AC drive reference select (set value = 02)
• Specify which of the option or AC drive references is used for operation. The option/AC drive
selection is effective only when the drive is stopped.
Open:
Option card frequency reference and operation signals are accepted.
Closed:
Frequency reference and operation signals from the AC drive control circuit
terminals or the digital operator are accepted.
4 Selection of multi-step speed references 1 to 3 and jog frequency select (set values = 3 to 6)
• Up to nine step speeds can be selected by combinations of multi-step speed references and
jog frequencies.
2-48
PA 7300
PART II: OPERATION MANUAL
Fig. 12 3-wire sequence
RUN COMMAND (RUNS WHEN "CLOSED")
PA7300
STOP COMMAND (STOPS WHEN "OPEN")
RUN
STOP
24VG
1
2
5
FWD/REV RUN SELECT
"OPEN": FWD RUN
"CLOSED": REV RUN
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...