(37) Auto Restart Time Interval
(Cn-62)
•
Set the auto reset / restart operation time interval when the number of auto reset /restart
operations is more than 2.
• The setting range of Cn-62 is 0~20 sec. The auto restart time interval is minimum baseblock
time (Cn-40) when the setting value of Cn-62 is 0.
• The auto restart time interval is the setting value of Cn-40 when the setting value of
Cn-62 < Cn-40.
• The auto restart time interval is the setting value of Cn-62 when the setting value of
Cn-62 > Cn-40.
(38) Motor Overheat Protection Time (Cn-63)
• Time delay for motor overheat protection when the detected temperature of PTC
thermistor motor temperature sensor reaches the trip level.
• Generally, Cn-63 should not be adjusted. The factory setting is at 150%, 1 minute motor
overheat capability.
• Refer to the motor overheat protection setting of Sn-19, on page 2-56.