5. TEST OPERATION
To assure safety, disconnect the coupling or belt which connects the motor with the machine prior to
test operation, so that motor operation is isolated. If an operation must be performed while the motor
is directly connected to the machine, use great care to avoid any possible hazardous conditions.
5.1 CHECK BEFORE TEST OPERATION
After completion of the installation and wiring, check for
(1) proper wiring
(2) short-circuit due to wire clippings
(3) loose screw-type terminals
(4) proper loading
5.2 SETTING THE LINE VOLTAGE JUMPER FOR 460V CLASS 40HP (30kW) AND ABOVE
The cooling fan line voltage jumper shown in Fig. 5 must be set according to the type of
main circuit power supply. Insert the connector at the position showing the appropriate line voltage.
The unit is preset at the factory to 440 line voltage.
(a) 460V CLASS: 40HP ~ 100HP
350HP ~ 500HP
(b) 460V CLASS: 125HP ~ 300HP
Fig. 5(a) Voltage Selection Jumper
5-1
PA 7300
PART I: INSTALLATION MANUAL