3. FAULT DISPLAY AND TROUBLESHOOTING
The PA7300 has protection function and warning self-diagnosis function. If a fault a occurs, the protection
functions operate to shut off the AC Drive output and the motor coasts to a stop. At the same time, the fault
contact signal (terminal R3A-R3C, R3B-R3C).
A). PROTECTION FUNCTION AND TROUBLESHOOTING
PROTECTION FUNCTION
EXPLANATION
LCD DISPLAY
(ENGLISH
)
Main circuit
When the AC Drive power voltage drops, torque becomes insufficient and the
low voltage
motor is overheated.
AC Drive output is stopped when the main circuit DC voltage becomes lower
Low
Momentary*
2
than the low voltage detection level for 15 ms or longer, or about 2 seconds
Fault (UV1)*
1
voltage
power loss
or longer if the momentary power loss ride-thru function is used.
DC Volt. Low
protection
protection
Detection level: Approximately 210V or less for 200V class
and 420V or less for 400V class
Control circuit
The AC Drive output is shut-off when the control circuit voltage drops below
Fault (UV2)*
1
low voltage
the low voltage level.
C/B DC Volt. Low
Man circuit
The AC Drive output is shut-off when no answer back is received from the
Fault (UV3)*
1
soft charge
main circuit soft-start contactor.
MC Ans. Fault
contactor defective
The AC Drive output is shut off when the AC Drive output current exceeds
Fault (OC)*
1
Overcurrent protection*
2
approx. 200% of AC Drive rated current.
Over Current
The AC Drive output is shut off when a ground-fault occurs at the AC Drive
Fault (GF)*
1
Ground-fault protection*
2
output side and the ground-fault current exceeds approximately 50% of the
Ground Short
AC Drive rated current.
The AC Drive output is shut off when the main circuit DC voltage exceeds
excessive because of regeneration energy caused by motor deceleration
Fault (OV)*
1
Overvoltage protection*
2
and negative load.
Over Voltage
Detection. Approx. 800V for input voltage set 400V and above
Level : Approx. 700V for input voltage set 400V or less and approx. 400V
for 200V class
The AC Drive output is shut off when the ambient temperature rises and the
Fault (OH)*
1
Cooling fin overheat*
2
heat sink fin reaches 90 °C . Please check for a detective cooling fan or
Over Heat
clogged filter.
AC Drive output is stopped when motor overload is detected by the
electronic thermal overload in the AC Drive. Either an AC Drive duty constant
Fault (OL1)*
1
Motor*
2
torque specialized motor or general-purpose motor can be selected. If more
Motor Over Load
than one motor is driven. overload protection should be disabled. Use a
Overload
thermal relay or thermal protector for each motor.
protection
AC Drive*
2
The AC Drive output is shut off when the electronic thermal overload reaches
or exceeds the inverse time limit of 103% of the AC Drive’s rated current
Fault (OL2)*
1
occurs. Maximum rated overload: 110%. 1 min.
AC Drive Over Load
Over torque*
2
The motor operates according to a preset mode when the AC Drive output
detection
current exceeds the overtorque detection level. This function is used to
Fault (OL3)*
1
protect the machine or to monitor the output torque.
Over Torque
Terminal 3
Fault (EF3)*
1
External Fault 3
Terminal 5
Fault (EF5)*
1
External
External Fault 5
fault
Terminal 6
When an external alarm signal is asserted. the AC Drive operates according to a
Fault (EF6)*
1
signal
preset stop method (coasting to a stop, continuous operation or ramp to stop)
External Fault 6
input
Terminal 7
Fault (EF7)*
1
External Fault 7
Terminal 8
Fault (EF8)*
1
External Fault 8
Control
Fault (CPF02)*
1
Circuit Fault
Logic board Fault
EEPROM
Fault (CPF03)*
1
fault
EEPROM Fault
EEPROM
BCC CODE
Fault (CPF04)*
1
Control
Error
EEPROM CODE Err.
Circuit
CPU ADC
The AC Drive output is shut off when a transmission error occurs in the
Fault (CPF05)*
1
Fault
Fault
control circuit or a component fails. The AC Drive output is also shut off
A/D Fault
Option Card
when a specialized option such as the digital operator is not properly connected.
Fault (CPF06)*
1
Fault
Opt. Card A/D Fault
3-1
PA 7300
PART II: OPERATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...