• CHARACTERISTICS
Control Method
Sine wave PWM
Frequency Control Range
0.1 to 180Hz
Frequency Accuracy
Digital command: 0.01% -10 to 40˚C\ +14 to 104˚F
Analog command: 0.1% 25 ± 10˚C\77 ± 18˚F
Frequency Setting Resolution
Digital operator reference: 0.01Hz,
Analog reference: 0.06Hz/60Hz
Output Frequency Resolution
0.01Hz (1/30000)
Overload Capacity
110% rated output current for one minute.
Frequency Setting Signal
0 to 10VDC (20KΩ), 4~20mA (250Ω), 0 ~ ± 10 VDC (option)
Accel/Decel time
0.1 to 6000 sec (independent Accel/Decel time settings)
Braking Torque
Approximately 20%
Type of. V/Hz patterns
(Total of 5)
1: For adjustable pattern.
4: For fans and pumps.
Motor Overload Protection
Electric thermal overload relay
Instantaneous Overcurrent
Motor coasts to stop at approx. 200% rated current.
Overload
Motor coasts to stop after 1 minute at 110% rated output current.
Overvoltage (230V class)
Motor coasts to stop if AC Drive output voltage exceeds 410VDC.
Overvoltage (460V class)
Motor coasts to stop if AC Drive output voltage exceeds 820VDC.
Overvoltage (600V class)
Motor coasts to stop if AC Drive output voltage exceeds 1050VDC
Undervoltage (230V class)
Motor coasts to stop if AC Drive output voltage drops to 190VDC or below.
Undervoltage (460V class)
Motor coasts to stop if AC Drive output voltage drops to 380VDC or below.
Undervoltage (600V class)
Motor coasts to stop if AC Drive output voltage drops to 546VDC or below
Momentary Power Loss
Motor coasts to stop after momentary power loss lasting over 15ms.
(time-setting made before shipment).
Motor Overheat Protection
Motor PTC thermistor (Active: 1330Ω, Return: 550Ω)
Input Phase Loss
Single phase protection.
Output Phase Loss
Provided by electronic circuit.
Fin Overheat
Thermostat
Stall Prevention
Stall prevention at acceleration/deceleration and constant speed operation.
Ground Fault
Provided by electronic circuit.
Power Charge Indication
Charge lamp stays ON until bus voltage drops below 50V.
Location
Indoor (Protected from corrosive gases and dust)
Ambient Temperature
Wall-mounted type: +14 to 104˚F (-10 to +40˚C ),(not frozen)
Open chassis type: +14 to 113˚F ( -10 to +45˚C ), (not frozen)
Storage Temperature
-4 to 140˚F (-20 to +60 ) °C
Humidity
95% RH (non-condensing)
Vibration
1G at 10 to 20Hz, up to 0.2G at 20 to 50Hz.
Communication Protocols
RS-485 MODBUS, PROFIBUS (option), METASYS (option), LONWORKS (option)
Noise Interference Suppression
EN 61800-3 (2000) with specified noise filter
Noise Immunity
EN61800-3 (2000)
7-3
PA 7300
PART I: INSTALLATION MANUAL
C
o
n
tr
ol Char
ac
teristics
Pr
ot
ec
tiv
e F
unc
tions
En
vi
ro
nm
en
ta
l
Co
nd
it
io
ns
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...