6. MAINTENANCE
6.1 PERIODIC INSPECTION
The PA7300 requires very few routine checks. It will function longer if it is kept clean, cool, and dry.
Observe precautions listed in “Location”, Section 3.2. Check for tightness of electrical connections,
discoloration, or other signs of overheating. Use Table 4 as your inspection guide. Before servicing,
turn OFF the AC main circuit power and make sure that the “CHARGE” lamp is OFF.
Table 4 Periodic Inspection
Component
Check
Corrective Act
ion
External terminals,
Loose screws
Tighten
unit mounting bolts,
connectors, etc.
Loose connectors
Tighten
Cooling fins
Blow with dry compressed
Build-up of dust and dirt
air of 39.2 ×10
4
to 58.8 x 10
4
Pa (57 to 85psi.) pressure.
Printed circuit board
Blow with dry compressed air
of 39.2 x10
4
to 58.8 x 10
4
Pa
Accumulation of conductive dust or oil
(57 to 85psi.) pressure. If dust
and or oil cannot be removed,
replace the board.
Cooling fan
Excessive noise and vibration, whether
the cumulative operation time exceeds
Replace the cooling fan.
20,000 hours or not.
Power elements
Blow with dry compressed air
Accumulation of dust and dirt
of 39.2 x10
4
to 58.8 x 10
4
Pa
(57 to 85psi) pressure.
Smoothing capacitor
Discoloration or odor
Replace the capacitor or
AC Drive unit.
Note: Operating conditions as follows:
•
Ambient temperature: Yearly average 30˚C , 86˚F
• Load factor: 80% or less
• Operating time: 12 hours or less per day
Standard Parts Replacement
Item
Replacement Cycle
Remarks
Cooling fan
2 or 3 years
Replace with a new product.
Smoothing capacitor
5 years
Replace with a new product.
(Determine after examination)
Circuit Breakers and relays
-----
Determine after examination.
Fuse
10 years
Replace with a new product.
Aluminum capacitor on PC
5 years
Replace with a new product.
board
(Determine after examination)
Note: Operating conditions as follows:
• Ambient temperature: Yearly average 30˚C, 86°F
• Load factor: 80% or less
• Operating time: 20 hours or less per day
6-1
PA 7300
PART I: INSTALLATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...