3.2 LOCATION
Location of the equipment is important to achieve proper performance and normal
operating life. The PA7300 should be installed in areas where the following conditions exist:
• Protection from rain or moisture.
• Protection from direct sunlight.
• Protection from corrosive gases or liquids.
• Free from airborne dust or metallic particles.
• Free from vibration.
• Free from magnetic noise (e.g. welding machines, power units)
• Ambient temperature:
+14 to 104˚F, -10 to +40˚C (For enclosed type)
+14 to 113˚F, -10 to +45˚C (For open chassis type)
• Free from combustible materials, gases, etc.
3-2
PA 7300
PART I: INSTALLATION MANUAL
CAUTION
When mounting multiple units in a common enclosure, install a cooling fan or some other
means to cool the air entering the AC Drive to at least 113ºF (45ºC) or below.