Function Parameter
Name
LCD Display
Setting Range
Setting
Factory
Reference
Number
(English)
Unit
Setting
Page
Cn-49
Tuning Operation
Cn-49=0.0%
0 ~ 20%
1%
0%
Voltage Limit
Sav. Tuning
V Limit
Energy
Cn-50
Tuning Operation
Cn-50=01.0s
0.1 ~ 10.0s
0.1s
1.0s
Savings
Control Cycle
Sav. Tuning Period
Tuning
Cn-51
Tuning Operation Voltage
Cn-51=00.5%
0.1 ~ 10.0%
0.1%
0.5%
2-22
Operation
Step (100% Output Voltage)
O/P Volt.100%
Cn-52
Tuning Operation Voltage
Cn-52=00.2%
0.1 ~ 10.0%
0.1%
0.2%
Step (5% Output Voltage)
O/P Volt. 5%
Cn-53
Not Used
Cn-53=00.000
00.000 ~ 00.000
--
--
--
Reserved
Cn-54
Not Used
Cn-54=00.000
00.000 ~ 00.000
--
--
--
Reserved
--
Cn-55
Not Used
Cn-55=00.000
00.000 ~ 00.000
--
--
--
Reserved
Cn-56
Not Used
Cn-56=00.000
00.000 ~ 00.000
--
--
--
Reserved
Cn-57
Not Used
Cn-57=00.000
00.000 ~ 00.000
--
--
--
Reserved
Cn-58
Energy Savings Coefficient
Cn-58=115.74*
6
0.00 ~ 655.35
0.01
115.74*
6
2-22
Energy
K2 (60Hz)
Eg. Saving Coeff
Savings
Cn-59
Energy Savings Coefficient
Cn-59=100%
50 ~ 100%
1%
100%
2-23
Coefficient
Reduction Ratio (6Hz)
K2 Reduce Ratio
K2
Cn-60
Motor Code
Cn-60=29*
4
00 ~ FF
--
29*
0
2-23
Reserved
--
Cn-61
Not Used
Cn-61=000
000 ~ 000
--
--
--
Reserved
Retry Time
Cn-62
Auto Restart Time Interval
Cn-62=00s
0 ~ 20s
1s
0s
2-24
Retry Time
Motor
Motor Overheat Protection
Cn-63=060s
Overheat
Cn-63
Time
Motor OH Time
1 ~ 300s
1s
60s
2-24
Time
*1 1 For 230V Class, x2 for 460V, x2.5 for 600V.
*2 For 230V Class, x2 for 460V, x2.5 for 600V.
*3 Setting range becomes 10 to 200% of AC Drive rated current. The factory setting base on TECO AEEF
standard 4 pole motor, 230V/60Hz, 460V/60Hz.
*4 Factory settings differ depending on AC Drive capacity (Sn-01 set value).
This example shows combination of TECO standard motor 460V 60Hz 25HP (18.5KW).
(Refer to the table on page 2-30 to 2-32)
At setting Sn-01, the set value changes to the factory setting. For any application other than TECO
standard motors, set the value shown on the nameplate of the motor.
*5 Factory setting and setting range differ depending on AC Drive capacity (Sn-01 set value).
*6 Differs depending on Cn-60 set value.
*7 Factory setting differ depending on V/F curve selection (Sn-02).
*8 The same value as Sn-01 is set.
2-12
PA 7300
PART II: OPERATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...