2-10
PA 7300
PART II: OPERATION MANUAL
2.3 Control Parameters Cn-
Function Parameter
Name
LCD Display (English)
Setting Range
Setting
Factory
Reference
No.
Unit
Setting
Page
Cn-01
Input Voltage
Cn-01=220.0V
150 ~ 255.0V*
1
0.1V
220.0V*2
Input Voltage
Cn-02
Max. Output
Cn-0=220.0V
50.0 ~ 180.0Hz
0.1Hz
60.0Hz*
7
Frequency
Max. O/P Freq.
Cn-03
Max. Output
Cn-03=220.0V
0.1 ~ 255.0V*
1
0.1V
220.0V
*2*7
Voltage
Max. Voltage
V/F
Cn-04
Max. Voltage
Cn-04=060.0Hz
0.1 ~ 180.0Hz
0.1Hz
60.0Hz*
7
2-13
Pattern
Frequency
Max. Volt Frequency
2-32
Setting
Cn-05
Middle Output
Cn-05=030.0Hz
0.1 ~ 180.0Hz
0.1Hz
30.0Hz*
7
Frequency
Middle O/P Freq
Cn-06
Voltage at Middle
Cn-06=055.0V
0.1 ~ 255.0V*
2
0.1V
55.0V*
1
*
7
Output Frequency
Middle Voltage
Cn-07
Min Output
Cn-07=001.5Hz
0.1 ~ 180.0Hz
0.1Hz
1.5Hz*
7
Frequency
Min O/P Freq.
Cn-08
Voltage at Min.
Cn-08=008.0V
0.1 ~ 255.0V*
2
0.1V
8.0V*
1
*
7
Output Frequency
Min. Voltage
Current
Cn-09
Motor Rated Current
Cn-09=031.0A
*3
0.1A
31A*
4
2-13
Base
Motor Rated I
Cn-10
DC Injection Braking
Cn-10=01.5Hz
0.1 ~ 10.0Hz
1.5Hz
1.5Hz*
7
Starting Frequency
DC Braking Start Freq.
DC
Cn-11
DC Braking Current
Cn-11=050%
0 ~ 100%
1%
50%
2-13
DC Braking Current
Braking
Cn-12
DC Injection Braking
Cn-12=00.0S
0.0 ~ 25.5s
0.1s
0.0s
2-14
Function
Time At Stop
DC Braking Stop Time
Cn-13
DC Injection Braking
Cn-13=00.0s
0.0 ~ 25.5s
0.1s
0.0s
Time At Start
DC Braking Start T
Frequency
Cn-14
Frequency Command
Cn-14=100%
0 ~ 109%
1%
100%
2-14
Limit
Upper Bound
Freq Cmd. Up Bound
Cn-15
Frequency Command
Cn-15=000%
0 ~ 109%
1%
0%
Lower Bound
Freq Cmd. Low Bound
Cn-16
Frequency Jump
Cn-16=000.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
Point 1
Freq Jump 1
Cn-17
Frequency Jump
Cn-17=0.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
Frequency
Point 2
Frequency Jump 2
Jump
Cn-18
Frequency Jump
Cn-18=0.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
2-15
Point 3
Freq Jump 3
Cn-19
Jump Frequency
Cn-19=01.0Hz
0.0 ~ 25.5Hz
0.1Hz
1.0Hz
Width
Freq. Jump Width
Display
Cn-20
Digital Operator
Cn-20=00000
0 ~ 39999
1
0
2-15
Unit
Display Unit
Disp.lay Unit 0.1Hz
Agreed
Cn-21
Frequency Agree
Cn-21=000.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
Speed
Detection Level
F Agree Det Level
Detection
Cn-22
Frequency Agree
Cn-22=02.0Hz
0.1 ~ 25.5Hz
0.1Hz
2.0Hz
2-16
Detection Width
F Agree Det Width
Cn-23
Carrier Frequency
Cn-23=6.0KHz
0.4 ~ 6.0KHz*
5
0.1KHz
6.0KHz*
5
Upper Limit
Carry-Freq. Up Bound
Carrier
Cn-24
Carrier Frequency
Cn-24=6.0KHz
0.4 ~ 6.0KHz*
5
0.1KHz
6.0KHz*
5
2-17
Frequency
Lower Limit
Carry-Freq. Low Bound
Cn-25
Carrier Frequency
Cn-25=00
0 ~ 99
1
0*
5
Proportional Gain
Carry-Freq. P_Gain
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...