Function
Parameter
Name
LCD Display
Description
Factory
Reference
No.
(English)
Setting
Page
- - -0: Overtorque detection disabled.
- - -1: Overtorque detection enabled
Operation mode
- -0 -: Enabled only if at agreed frequency
2-40
Sn-07
Selection 4
Sn-07=0000
- -1 -: Enable during operation
0000
2-41
(overtorque
Over Tq. Detect
(except during DC injection)
detection)
- 0- -: Operation continued after
overtorque is detected
- 1- -: Coasts to stop if overtorque is detected
- - -0: Frequency reference input by
RS-485 communication option
card (PA-M or PA-P)
- - -1: Frequency reference input by
digital operator or control circuit
Operation
input terminals
Mode Select
- -0 -: RUN/STOP command input by
RS-485 Communication option
Operation Mode
Sn-08=0111
card (PA-M or PA-P)
Sn-08
Selection 5 (RS-485
RS-485 Comm.
- -1 -: RUN/STOP command input by
communication
Function
digital operator or control circuit
0011
2-41
status selection)
input terminals
2-42
00- -: RS-485 communication fault,
deceleration to stop (Bn-02)
01- -: RS-485 communication fault,
coast to stop
10- -: RS-485 communication fault,
deceleration to stop (Bn-04)
11- -: RS-485 communication fault,
continue to run
Operation Mode
Sn-09=0000
- 0- -: Energy-savings function disabled.
Sn-09
Selection 6
Eng. Saving Function - 1- -: Energy-savings function enabled
.
0000
2-42
(Energy Savings Func.)
- - -0: Stall prevention during
acceleration enabled
- - -1: Stall prevention during
acceleration disabled
- -0 -: Stall prevention during
deceleration enabled
Protective
- -1 -: Stall prevention during
Sn-10
Characteristic
Sn-10=000
deceleration not enabled
Selection 1
Stall Select
- 0- -: Stall prevention during run enabled
0000
2-42
Protective
(Stall Prevention)
- 1- -: Stall prevention during run disabled
2-43
Characteristics
0- - -: Decel time during stall prevention=
Select
Bn=02 set value
1- - -: Decel time during stall prevention=
Bn=04 set value
- -0 -: Fault contact is not energized
Protective
during Retry operation
Characteristic
- -1 -: Fault contact is energized
Sn-11
Selection 2
Sn-11=0000
during Retry operation
(Retry and
Retry & Ride Thru
-0 - -: Operation stopped by
0000
2-43
Momentary Power
momentary power loss
2-44
Failure Protection)
detection (UV1)
-1 - -: Operation continues after
momentary power loss
2-26
PA 7300
PART II: OPERATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...