Function
Parameter
Name
LCD Display
Description
Factory Reference
No.
(English)
Setting
Page
Sn-23
Inverter Station
Sn-23=01
Inverter address can be set betweem 1 and 31
01
Address
Inverter Address
- -00: No parity
RS-485
- -01: Even parity
parity setting
Comm.
- -10: Odd parity
2-62
Function
Sn-24
RS-485 Comm.
Sn-24=0011
- -11: not used
0011
Protocol Setting
RS-485 Protocol
00- -: 2400 bps (bit/sec)
01- -: 4800 bps baud
10- -: 9600 bps rate
11- -: 19200 bps setting
Language
Sn-25
LCD Language
Sn-25=0
0:
English
Displayed Selection
Language: Select
1:
Chinese
0
2-63
0:
Frequency command (10V/max
frequency command, Cn-02)
1:
Output Frequency (10V/max Output frequency)
Multi-Function
Sn-26=00
2:
Output Current (10V/AC Drive rated current)
Sn-26
Analog Output AO2
Term. A01
3:
Output Voltage (10V/input voltage, Cn-01)
0
2-63
Function Selection
Function
4:
DC Voltage (10V/400VDC or 800VDC)
Multi-Function
5:
Output Power (10V/max. applicable
Analog Output
motor capacity)
Selection
0:
Frequency command (10V/max
frequency command, Cn-02)
1:
Output Frequency (10V/max
Output frequency)
Sn-27
Multi-Function
Sn-27=01
2:
Output Current (10V/AC Drive rated current)
Analog Output AO2
Term. A02
3:
Output Voltage (10V/input voltage, Cn-01)
1
2-63
Function Selection
Function
4:
DC Voltage (10V/400VDC or 800VDC)
5:
Output Power (10V/max. applicable
motor capacity)
--
Sn-28
Not Used
Sn-28=0
--
--
--
Reserved
--
Sn-29
Not Used
Sn-29=0
--
--
--
Reserved
0:
1-8 PID Relay Card ineffective
1:
Fixed inverter drive mode, stop all the
pumps by first-run-last-stop sequence.
2:
Fixed inverter drive mode, stop the
PA-PID Card
pump driven by the AC Drive only.
Function
Sn-30
Pump Operation
Sn-30=0
3:
Fixed inverter drive mode, stop all the
0
2-64
Selection
Mode Selection
Run-Mode Select
pumps by first-run-first-stop sequence.
4:
Cycled inverter drive mode, stop all
the pumps by first-run-first-stop sequence.
5:
Cycled inverter drive mode, stop the pump
driven by the Inverter only.
2-28
PA 7300
PART II: OPERATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...