4.4 WIRING PARTS
4.4.1 RECOMMENDED WIRING PRACTICE
Be sure to connect MCCBs between the power supply and PA7300 input terminals L1 (R),
L2 (S), L3 (T). Recommended MCCBs are listed in Table 3.
When a ground fault interrupter is used, select one with no influence on high frequency. The
current setting should be 200mA or higher and operating time at 0.1 second or higher to
prevent malfunction.
Table 3 Applicable Wire and Contactor Size
(a) 230V SERIES
MAX. APPLICABLE
CABLE SIZE - MM2 (AWG)
MOTOR OUTPUT
MOLDED-CASE
MAGNETIC
HP (KW)
POWER CABLE
GROUND CABLE E CONTROL CABLE CIRCUIT BREAKER
CONTACTOR
[NOTE 1]
[NOTE 2]
[G]
[NOTE 3]
[NOTE 4]
[NOTE 4]
5(3.7)
5.5
5.5
0.5~2
TO-50EC
(30A)
CN-16
7.5(5)
8
5.5~8
0.5~2
TO-100S
(50A)
CN-18
10(7.5)
8
5.5~8
0.5~2
TO-100S
(60A)
CN-25
15(11)
22
8
0.5~2
TO-100S
(100A)
CN-50
20(15)
22
8
0.5~2
TO-100S
(100A)
CN-65
25(18.5)
22
14
0.5~2
TO-225S
(4)
(6)
(20-14)
(150A)
CN-80
30(22)
22
14
0.5~2
TO-225S
(4)
(6)
(20-14)
(175A)
CN-100
40(30)
60
22
0.5~2
TO-225S
(2/0)
(4)
(20-14)
(175A)
CN-125
50(37)
60
22
0.5~2
TO-225S
(2/0)
(4)
(20-14)
(200A)
CN-150
60(45)
60×2P
22
0.5~2
TO-225S
(2/0×2P)
(4)
(20-14)
(225A)
CN-180
75(55)
60×2P
30
0.5~2
TO-400S
(2/0×2P)
(2)
(20-14)
(300A)
CN-300
100(75)
100×2P
50
0.5~2
TO-400S
(4/0×2P)
(1/0)
(20-14)
(400A)
CN-300
125(90)
100×2P
50
0.5~2
TO-400S
S-K400
(4/0×2P)
(1/0)
(20-14)
(400A)
(Note 5)
Note:
1. For constant Torque Load
2. Power Cable Includes Cables to the Control Terminals. R(L1), S(L2), T(L3), , , B2, U(T1), V(T2), W(T3).
3. Control Cable includes Cables to the Control Terminals.
4.The Molded-Case Circuit Breakers and Magnetic Contactors Shown in Table 3 are TECO Products and are for reference only.
Other manufacturer’s equivalents may be selected.
5. The Magnetic Contactors S-K400 and S-K600 are Mitsubishi Products and are for reference only. Other manufacturer’s
equivalents may be selected.
4-5
PA 7300
PART I: INSTALLATION MANUAL
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...