Fac
tor
y S
et
Inverter Drive Capacity Selection
460V Class
Name
Sn-01 Value 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37 38
PA7300-
4
-N1
005 007 010 015 020 025 030 040 050 060 075 100 125 150 175 200 250 300 350 400 500
AC Drive rated capacity
(KVA)
6.2 9.3 12.4 18.6 24.8 29 34
45 57 66
85 115 144 176 203 232 259 290 393 446 558
Max. applicable motor capacity HP
5 7.5 10 15 20
25 30
40 50 60
75 100 125 150 175 215 250 300 350 400 500
(kW) (3.7) (5) (7.5) (11) (15) (18.5) (22) (30) (37) (45) (55) (75) (90) (110) (132) (160) (185) (220) (260) (300) (375)
AC Drive rated current
(A)
8
12 16 24 32
38 44
59 75 86 111 151 189 231 267 304 340 380 516 585 732
Cn-09 Motor rated current
(A)
6.8 10.1 12.6 18.6 24.8 31 36
49 59 71
88 114 143 175 205 235 305 348 410 465 582
Cn-23 Carrier frequency
10.0 10.0 10.0 10.0 10.0 6.0 6.0 6.0 6.0 6.0 6.0 3.0 3.0 3.0 3.0 3.0 3.0 2.0 2.0 2.0 2.0
upper limit
(kHz)
Cn-24 Carrier frequency
10.0 10.0 10.0 10.0 10.0 6.0 6.0 6.0 6.0 6.0 6.0 3.0 3.0 3.0 3.0 3.0 3.0 2.0 2.0 2.0 2.0
lower limit
(kHz)
Cn-25 Carrier frequency
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
proportional gain
On-17 Motor phase-to-phase
2.735 1.776 1.151 0.634 0.436 0.308 0.239 0.164 0.13 0.110 0.074 0.027 0.036 0.023 0.020 0.022 0.014 0.012 0.01 0.009 0.007
resistance
(Ω)
On-18 Torque compensation
208 252 285 370 471 425 582 536 641 737 790 1800 2900 2500 2600 2500 2600 2800 2400 3200 3600
iron loss
(W)
On-19 Torque compensation
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
limit
(V)
Cn-37 Momentary power
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
loss assurance time
(s)
Cn-40 Minimum baseblock time (s) 0.5 0.7 0.7 0.7 0.7 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Cn-41 V/f during speed search (%) 100 100 100 100 100 100 100 100 100 100 80 80
80 80 80 80 80 80
80 80
80
600V Class
Name Sn-01 Value
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
PA7300-
4
-N1
5005
5008
5010
5015
5020
5025
5030
5040
5050
5060
5075
5100
AC Drive rated capacity
(KVA)
6
8.9
10.9
16.9
22
27
32
41
52
62
77
99
Max. applicable motor capacity
5
7.5
10
15
20
25
30
40
50
60
75
100
HP(kW)
(3.7)
(5)
(7.5)
(11)
(15)
(18.5)
(22)
(30)
(37)
(45)
(55)
(75)
AC Drive rated current
(A)
6.1
9
11
17
22
27
32
41
52
62
77
99
Cn-09 Motor rated current
(A)
5.1
7.5
9.6
14.4
18.9
23.1
27.6
36.2
44.9
55.3
68.5
95
Cn-23 Carrier frequency
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
4.0
upper limit
(kHz)
Cn-24 Carrier frequency
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
4.0
lower limit
(kHz)
Cn-25 Carrier frequency
0
0
0
0
0
0
0
0
0
0
0
0
proportional gain
On-17 Motor phase-to-phase
4.939
2.601
1.446
1.171
0.896
0.658
0.518
0.438
0.267
0.21
0.15
0.099
resistance (Ω)
On-18 Torque compensation
130
193
263
385
440
508
586
750
925
1125
1260
1600
iron loss
(W)
On-19 Torque compensation
143
143
143
143
143
143
143
143
143
143
143
143
limit
(V)
Cn-37 Momentary power
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
loss assurance time
(s)
Cn-40 Minimum baseblock
time
(s)
0.5
0.5
0.5
0.5
0.5
0.5
1.0
1.0
1.0
1.0
1.0
1.0
Cn-41 V/f during speed search (%)
100
100
100
100
100
100
80
80
80
80
80
80
2-31
PA 7300
PART II: OPERATION MANUAL
Fac
tor
y S
et
Summary of Contents for PA7300 Series
Page 9: ......
Page 10: ...PART I INSTALLATION MANUAL ...
Page 44: ...PART II OPERATION MANUAL ...
Page 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Page 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Page 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Page 150: ...i PA 7300 INSTRUCTION MANUAL ...
Page 151: ...i PA 7300 INSTRUCTION MANUAL ...
Page 152: ...i PA 7300 INSTRUCTION MANUAL ...
Page 153: ...i PA 7300 INSTRUCTION MANUAL ...
Page 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...