O
utput Char
ac
teristics
Po
w
er Supply
600V CLASS
AC INVERTER (HP)
5
7.5
10
15
20
25
30
40
50
60
75
100
MAX. APPLICABLE MOTOR
5
7.5
10
15
20
25
30
40
50
60
75
100
OUTPUT HP (KW)*1
(3.7)
(5)
(7.5)
(11)
(15)
(18.5)
(22)
(30)
(37)
(45)
(55)
(75)
AC Drive
Capacity
6.0
8.9
10.9
16.9
22
27
32
41
52
62
77
99
(KVA)
Rated Output
Current (A)
6.1
9.0
11
17
22
27
32
41
52
62
77
99
Max. Output
3-Phase, 500/550/575/600V
Frequency
(Proportional to input voltage)
Rated Output
Up to 180Hz available
Frequency
Rated Input
Voltage And
3-Phase, 500~600V
Frequency
50/60Hz
Allowable
Voltage
+10% ~ -15% Power Supply
Fluctuation
Allowable
Frequency
±5%
Fluctuation