2-2
Hardware Installation Procedure
Coral IPx Office Installation Manual
Si
te Inspection
2
5.
Verify that ventilation of the installation area is capable of maintaining an
ambient temperature of 32
°
-104
°
F (0
°
-40
°
C), and a relative humidity of
20-80% non-condensing, considering the system nominal heat dissipation
700 BTU/hr. (These figures are for each cage only, and do not take into
account heat generated by other equipment.)
6.
Verify that the installation area is free of caustic or corrosive liquids,
substances, or materials. Check local building codes for additional
requirements.
7.
Verify that the installation area is located no closer than 20ft (6.1m) from
electric devices that produce large electro-magnetic fields or high levels of
radio frequency energy. Possible sources are radio transmitters, electric arc
welding machines, copying machines, electric motors, refrigeration units,
power transformers, electric load centers, and main circuit breaker panels.
8.
Verify that the installation area provides reasonable security to the system.
Room construction should include solid, reinforced walls and a locking door.
0
This section describes the Coral IPx Office space requirements.
9.
Verify that there is sufficient space for the Coral IPx Office system
components.
10.
The dimensions and weights of the various components are provided in
.
11.
A minimum clearance, as detailed in
, must be provided around the
the various system components. For more detailed information, see
12.
displays a schematic diagram of all installation orientation options.
13.
The cage must be mounted horizontally.
14.
The mounting of an optional expansion cage should be taken into
consideration when mounting the Coral IPx Office equipment.
15.
For safety reasons, the top cover of the IPx Office unit must not be positioned
higher than 64" (162.5 cm) from the floor.
16.
Sufficient space must be reserved for any additional equipment related to the
Coral IPx Office system, such as the Program Interface terminal or personal
computer, voice mail system, external public address system, etc.
...................................................................................................
2
Space Requirements
Summary of Contents for Coral IPx Office
Page 2: ......
Page 4: ......
Page 25: ...xxi Figure 11 10 WiFi Antenna Removal 11 18...
Page 26: ......
Page 28: ......
Page 36: ...1 8 Introduction Coral IPx Office Installation Manual About this Manual 1 NOTES...
Page 44: ......
Page 96: ......
Page 106: ...3 10 Initial Power up Tests Coral IPx Office Installation Manual Common Control Test 3 NOTES...
Page 122: ......
Page 138: ......
Page 182: ......
Page 234: ......
Page 258: ...7 24 Power Supply Coral IPx Office Installation Manual PS Office DC Power Supply Unit 7 NOTES...
Page 260: ......
Page 302: ...8 42 Common Control Cards Coral IPx Office Installation Manual Compact Flash Disk 8 NOTES...
Page 310: ...8 50 Common Control Cards Coral IPx Office Installation Manual DBM Card 8 NOTES...
Page 312: ......
Page 372: ...9 60 Shared Service Cards Coral IPx Office Installation Manual VoIP Media Gateway MG 9 NOTES...
Page 420: ......
Page 488: ......
Page 509: ......