NICE3000
new
User Manual Description of Function Codes
- 171 -
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-48
Emergency evacuation
switching speed
0.010–0.630
0.010
m/s
★
It is used to set the switching speed at shorting stator braking mode switched over to
controller drive via speed setting.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-49
Evacuation parking floor
0 to F6-01
0
s
★
It is used to set the evacuation parking floor when Bit2 (Stopping at evacuation parking floor)
in F6-45 is enabled.
Group F7: Test Function Parameters
This group of parameters is specialized for elevator commissioning.
Follow the instructions for normal-speed commissioning:
1. Before the commissioning, ensure that the shaft is unobstructed and the related
parameters have been set properly.
2.
Run the elevator to the middle floor of the shaft at the inspection speed so as to prevent
wrong running direction.
3.
Perform single-floor command commissioning and then perform multi-floor command
commissioning.
4. After the commissioning is complete, check that the parameters in this group are set
properly.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F7-00
Car call floor registered
0 to F6-00
0
-
☆
F7-01
Up call floor registered
0 to F6-00
0
-
☆
F7-02
Down call floor registered
0 to F6-00
0
-
☆
These parameters are used to set the destination floors at elevator commissioning or
repairing. They can be respectively used as the car call button, hall call up button and hall
call down button. They remain valid after the commissioning command is input, and become
invalid until they are set to 0 or the system suffers power failure.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F7-03
Random running times
0–60000
0
-
☆
It is used to set the random running times of the system.
The NICE3000
new
has the random automatic running function. If the setting of F7-03 is
greater than 60000, the system keeps implementing random automatic running until you set
F7-03 to 0.
You can set the time interval between two times of random running in F7-08.
Summary of Contents for NICE3000 New
Page 1: ......
Page 13: ......
Page 14: ...1 Safety Information and Precautions ...
Page 21: ...Safety Information and Precautions NICE3000new User Manual 20 ...
Page 22: ...2 Product Information ...
Page 33: ...Product Information NICE3000new User Manual 32 ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 67: ...4 Use of the NICE3000new ...
Page 79: ...5 System Commissioning and Application Example ...
Page 105: ...6 Function Code Table ...
Page 136: ...Function Code Table NICE3000new User Manual 134 ...
Page 137: ...7 Description of Function Codes ...
Page 205: ...8 EMC ...
Page 214: ...EMC NICE3000new User Manual 212 ...
Page 215: ...9 Troubleshooting ...
Page 230: ......
Page 233: ......