Sunny Boy 700
Technical Description
SB700-11:EE
-
44
-
SMA Regelsysteme GmbH
Blinking code 4: Input voltage (PV-panel) too high
The yellow failure indication LED is activated for 5 seconds, is out for 3 seconds and
then blinks four times. The code is sent three times.
If the failure consists the indication is repeated.
The input voltage is too high. The PV-panels are generating a voltage higher than the
permissible specified voltage!
Disconnect the grid and then the PV-panels from the Sunny Boy immedi-
ately. Too high input voltages can cause a non-repairable damage.
Have the circuits of your PV-panels checked by your electrician. The permissible PV
input voltage of the Sunny Boy is listed in the technical data in chapter 9.