Sunny Boy 700 Technical Description Download Page 1

SB700-11:EE0502 

String Inverter for Photovoltaic Plants 

 

Issue 1.0 

Technical Description 

Sunny Boy 700 

Summary of Contents for 700

Page 1: ...SB700 11 EE0502 String Inverter for Photovoltaic Plants Issue 1 0 Technical Description Sunny Boy 700 ...

Page 2: ...0 Issue and Alteration Review 1 Comments Author 11 EE0502 1 0 A Translation from German Issue 1 0 Simon 1 A Changes due to faulty documents or improvement of the documentation B Changes maintaining full or upward compatibility C Changes limiting or excluding compatibility Name Date Signature Approved Bremicker ...

Page 3: ... following description of symbols This indicates a feature that is important either for optimal and comfortable usage or optimal operation of the system Example To keep string voltage low we recommend the following proce dure This indicates a fact or feature which is very important for the safety of the user and or which can cause a serious defect if not applied appropriately Example Disconnect th...

Page 4: ...n to the Electricity Grid 23 3 3 2 Connection of the PV panels 25 4 Commissioning 30 5 Operation and Failure Indication LEDs 32 5 1 Opening and closing of the Sunny Boy 46 6 System Monitoring and Diagnosis 49 6 1 Data Transmission via Powerline 49 6 2 Data Transmission with a Separate Data Cable 51 6 3 Upgrading or modification of the Sunny Boy interface 59 6 4 Graphic User Interface under Windows...

Page 5: ...ng Inverter may only be opened by qualified per sonnel for both maintenance and modification The device can still be charged with very high hazardous voltages even when disconnected For optimal safety closely follow all steps as described in the chap ters 3 Installation and 5 1 Opening and closing of the Sunny Boy ...

Page 6: ...association Berufsgenossenschaft für Feinmechanik und Elektrotechnik concerning the Inde pendent Disconnection Device known as MSD Mains monitoring device with allo cated Switching Devices and the regulations of the DIN VDE 0126 Furthermore the Sunny Boy complies with the according harmonised standards and the low voltage regulations as certified in the CE declaration see appendix In the following...

Page 7: ...nel to grid compatible AC voltage with so called inverters and the subsequent connection to the electricity grid in the house distribution Here the electricity from the PV modules provides all consumers with electric power household devices lights etc In case that not enough energy is produced the addi tionally necessary energy is obtained from the grid In case that there is a surplus of energy th...

Page 8: ...d system design for PV plants String Technology means that a small number of PV modules are connected in se ries to a string each string is then connected to a separate inverter which feeds the electricity of one string to the grid Large PV plants consist of a large number of sin gle strings The energy produced is collected directly on the AC side making the sys tem design very simple No extra DC ...

Page 9: ...for direct data acquisition Sunny Data The PC program for communication with your Sunny Boy inverters Sunny Boy Control Family The intelligent control terminals for your PV plant for data acquisition visualisa tion and saving Sunny Data Control The PC program for visualization of data from your Sunny Boy Control SMA is the European market leader for inverters for photovoltaic applications with ove...

Page 10: ...PC and the single inverters is normally done via Powerline communication see chapter 6 1 The Sunny Boy String Inverters support the following monitoring concepts developed by SMA PC with Sunny Data for Windows for small and medium size PV plants also with Sunny Boy Control Sunny Boy Control as stand alone controller for any PV plant size PC with Sunny Data Control for Windows together with a Sunny...

Page 11: ...uit diagram of the Sunny Boy 700 The PV input voltage range of the Sunny Boy 700 is designed for up to 10 standard PV modules It can be configured with three different voltage ranges so that even small PV panel power can be optimally utilized see chapter 3 3 2 The current fed to the grid is perfectly sinus shaped and has a very low harmonic distortion due to the fact that a one chip computer manag...

Page 12: ...ces German ENS This means the Sunny Boy can be connected to the in house network at practically every spot which substan tially simplifies its installation The relevant regulations and standards of course must be kept to The case is made of stainless steel which protects the inverter from dust and water up to IP 65 The Sunny Boy can therefore be mounted nearly anywhere inside or outside the house ...

Page 13: ...er is equipped with an independent disconnection device that has been certified by the Berufsgenossenschaft für Feinmechanik und Elektrotechnik The regulation is called Automatic disconnecting facility for photovoltaic installations with a nominal output 4 6 kVA and a single phase parallel feed by means of an inverter into the public low voltage mains For maximum safety this independent disconnect...

Page 14: ...grid voltage UN Once the grid voltage exceeds this range the Sunny Boy is disconnected from the grid within 0 2 s Grid Frequency The grid frequency may be within a range of 0 2 Hz of the nominal grid frequency fN while the voltage is within a range of 30 and 15 of the nominal grid voltage Un once the frequency goes beyond this range the Sunny Boy is disconnected from the grid within 0 2 s Furtherm...

Page 15: ...ter to the customer For the user this means The intensive testing of the disconnection device by the electricity company and the installer and periodic checking of the disconnection device legally required previously are not necessary anymore The redundant design of the MSD and the regular self test on startup allow the user to get along without periodic tests Each startup includes a function test...

Page 16: ... a sturdy packaging which can be recycled the inverters can be dam aged in transit which is usually the forwarder s fault Please inspect your inverter thoroughly after it is delivered If any damages can be detected on the packaging that could make you conclude the contents is damaged or if you detect that the inverter is damaged please immediately notify the forwarding company SMA or your local su...

Page 17: ...und for the inverter s while the PV plant is designed To find the optimum location please consider the following most important criteria Criteria for device mounting Due to the high protection class IP65 the installation is possible indoors and outdoors If possible do not expose the inverter to direct moisture despite IP65 Keep the DC cabling from the solar generator to the inverter as short as po...

Page 18: ...reduce the energy yield if necessary install a sun shield A minimum distance of 200 mm must be clear above the inverter for ventilation i e no cupboards ceiling etc The free air circulation around the case must not be obstructed to ensure sufficient cooling If you install the Sunny Boy in a cabinet or closet etc the air circula tion must be sufficient for heat dissipation provide external ventila ...

Page 19: ...installation of the Sunny Boy and are included in the packing list Sunny Boy 700 Drilling template in appendix 1 pc AC connection socket set 1 pc Seal for AC connection socket 1 pc Seal for MC plug 1 pc Seal for MC socket 1 pc Cable gland PG16 1 pc Tabelle 3 1 Packing list for mounting and installation Fig 3 2 Picture of drilling template original template in appendix ...

Page 20: ...crews and 8 mm dowels For outside mounting use stainless steel screws If necessary plastic washers should be inserted between the screw and metal strap in order to avoid scratching the paint when screwing Fig 3 3 Side view of mounting to wall Metal straps for mounting The top straps take the load the bot tom is screwed down in order to pre vent tilting off the wall Securing the Sunny Boy against l...

Page 21: ...rk the holes with the drilling template Drill the holes and put in the dowels put in the screws of both top holes and screw them in until ca 4 mm are sticking out Hang the inverter into the two top screws Fasten the bottom screw in order to prevent lifting up Check the mounting of the inverter ...

Page 22: ...rom the PV string and the AC voltage of the utility must be done in the order de scribed here This ensures that the disconnecting of contacts as well as hazardous voltages during the installation are avoided 1 Connect to the electricity grid see chapter 3 3 1 2 Connect the PV string see chapter 3 3 2 3 Connect the PV string to the Sunny Boy 4 Connect the utility by putting the AC fuse on Disconnec...

Page 23: ... of the electricity grid impedance at house dis tribution and all impedance values of cables and clamping points NB Impedance values are ca 0 48 Ω for a 20 m cable with a cross section of 1 5 mm ca 0 50 Ω for a 35 m cable with a cross section of 2 5 mm The AC connector socket for utility connection can take a cross section of up to 2 5 mm Make sure the grid is disconnected in the fusebox before yo...

Page 24: ...through the socket tube Connect the wires of the AC cable as follows Protective Earth PE to the terminal with the ground symbol Neutral wire to the terminal marked with 1 Phase L to the terminal marked with 2 The terminal marked with 3 is not used Make sure that all wires are firmly connected Push the socket tube firmly onto the socket Screw the cable seal firmly onto the socket tube For cables th...

Page 25: ...ance of the and poles to PE The red LED is switched on whenever resistance is below 1 MΩ see chapter 5 Operation and Failure Indication LEDs The voltage between the and pole of the PV modules string volt age can be lethal The circuit that monitors the insulation results in a slight electric connection to the PE The very high resistance of the circuit normally prevents a dangerous current from flow...

Page 26: ...6 modules are possible which produce a voltage of 100 V to 200 V DC or 75 V to 150 V DC Reduction of the input voltage results in a reduction of the output power of the Sunny Boy 700 100 V to 200 V results in a nominal output power of 600 W 75 V to 150 V results in a nominal output power of 450 W It may be necessary to configure the Sunny Boy 700 input voltage range according to the number of conn...

Page 27: ...escription SB700 11 EE 27 SMA Regelsysteme GmbH Fig 3 5 Position of adapter block and jumpers 5 1 releaseinternal clamp withscrewdriver 2 insert cableinconnector andrem ove screwdriver Fig 3 6 How to fix cable in adapter block ...

Page 28: ... voltage Adapter connector block Jumpers 125 V 250 V DC default on connector both Jumpers stay 100 V 200 V DC connector on remove this Jumper open leave this Jumper 75 V 150 V DC connector on leave this Jumper open remove this Jumper Table 3 1 Configuration of the input voltage Close the Sunny Boy as described in chapter 5 1 ...

Page 29: ... string or two parallel strings Therefore there are two connections for both the and the pole Within the device these connections are connected in parallel each Should you be working with one single string connection please close the unused plug in contacts on the Sunny Boy by the seals provided with the delivery Before connecting the snap cable connectors of the PV panel to the Sunny Boy check th...

Page 30: ... have full contact As soon as the PV panel has been connected via the Multi Contact plug connectors internal PV panel voltage is on Connect the grid voltage by closing the circuit breaker of the supply lead If the input voltage is high enough the Sunny Boy should start to feed inverted PV power fully automatically to the grid once enough power is coming from the PV modules The design of the Sunny ...

Page 31: ... The internal consumption is negligible for the voltage measurement with higher solar radiation The operating state of the Sunny Boy will be indicated with three LEDs integrated into the lid The meaning of the LEDs will be explained in chapter 5 Operation and Failure Indication LEDs ...

Page 32: ...de if the radiation and the result ing electric input energy is too low and is therefore always ready for operation Each time the Sunny Boy starts up it runs a number of self tests and safety proce dures The green LED Operation indicates the current operation The red LED warns the user that an Earth Fault has occurred A description of this situation and what has to be done in that case is given in...

Page 33: ... 11 EE 33 SMA Regelsysteme GmbH Fig 5 1 Front view of part of the Sunny Boy Description of the symbols used in the following section LED off LED blinks once per second LED blinks fast ca three times per second LED is constantly on not relevant ...

Page 34: ...ly initiated condition green red yellow waiting checking grid starting conditions are being checked green red yellow feeding grid MPP or constant voltage mode normal operation green red yellow isolation failure earth fault of the PV panels or failure of surge voltage protection green red yellow failure internal or external failure exact descrip tion depending on blink code green red yellow permane...

Page 35: ...e input voltage is too low UPV approx 60 V to supply the Sunny Boy control system with enough power Initialization All LEDs are on The Sunny Boy control system is initializing The string voltage to the inverter is above approx 60 V The supply is sufficient for the system control and not quite sufficient for feeding to the grid Data transmission is not possible yet ...

Page 36: ...ing Stop condition can be initiated by the user with the Sunny Boy Control or the pro gram Sunny Data The Sunny Boy remains in this condition until set to MPP Operation or Constant Voltage Operation or until reinitialized e g after system shutdown Waiting Grid Monitoring Green LED blinking once per second Red LED off Yellow LED off The Sunny Boy is checking the grid concerning its suitability for ...

Page 37: ...e MPP voltage of the PV panel which is internally defined as PV setpoint voltage In MPP mode the maximum power point PAC is set by changing the required PV voltage at the PV panel Constant Voltage mode The voltage from the PV modules can be set to a fixed value This value U Konst can be manually defined by the operator and transmitted to the Sunny Boy via the Sunny Boy Control or with the Sunny Da...

Page 38: ...ent pass The possible failures are described in the following together with the methods to find out how to distinguish the reasons for the failure Insulation failure Failure at the PV panel or PV connection The plus or minus pole from the PV panel or one of the PV modules has a connection 1 MΩ to the grounding earth PE The repair of an insulation failure must be conducted by quali fied personnel A...

Page 39: ...ndition is indicated with the Erdschluß Earth Fault LED The replacement of a thermally monitored varistor should be conducted by qualified personnel Determining the Failure The red LED indicates one of the above mentioned failures A short description on how qualified personnel can distinguish between these and conduct the ap propriate countermeasures is given in the following Please take note of a...

Page 40: ...anels by pulling the Multi Contact plug connectors Wait 5 minutes until the internal voltage has discharged Remove the bridges from 2 to 3 in the two connector blocks Mount a bridge from connector 2 in one connector block to connector 2 in the other connector block Re connect the PV panels and the grid to the Sunny Boy If the red LED is still on the Sunny Boy is damaged and must be repaired by the...

Page 41: ...eration Earth Fault Failure The yellow failure LED is permanently on This is a failure of the grid monitoring or the autonomous disconnection device MSD The Sunny Boy has detected a failure in the autonomous disconnection facilities and has suppressed the grid feeding Further proceedings are described in chapter 7 ...

Page 42: ...oltage VAC min see High grid voltage VAC max Low grid frequency fAC min High grid frequency fAC max Drastic change of frequency dFAC Check the electric grid supply check the function of other electric consumers and check the fuse of the mains connector to the Sunny Boy If you do not find any failure have the grid connection to the Sunny Boy checked by a qualified electrician Check the correct conn...

Page 43: ...y has detected a failure based on non permissible grid impedance val ues The criteria for the grid impedance are described in the section MSD A too high grid impedance can be the reason in case this failure occurs very often forcing the inverter to switch off The impedance can be checked with the Sunny Boy Control or Sunny Data Should the impedance be ZAC 1 25 Ω the Sunny Boy may not connect to th...

Page 44: ...s If the failure consists the indication is repeated The input voltage is too high The PV panels are generating a voltage higher than the permissible specified voltage Disconnect the grid and then the PV panels from the Sunny Boy immedi ately Too high input voltages can cause a non repairable damage Have the circuits of your PV panels checked by your electrician The permissible PV input voltage of...

Page 45: ...on LED is activated for 5 seconds is out for 3 seconds and then blinks five times The code is sent three times If the failure consists the indication is repeated The Sunny Boy is in a condition that makes it impossible to return to normal opera tion and is most likely defect The Sunny Boy has to be checked by a qualified technician ...

Page 46: ... up the input voltage range follow the instructions given below Opening of the Sunny Boy The Sunny Boy must only be opened by a qualified electrician When working on the Sunny Boy follow the instructions below 1 Separate the Sunny Boy from the grid by opening the circuit breaker 2 Separate all poles of the Sunny Boy from the PV panel by pulling the MC plug connectors Wait for approx 5 minutes unti...

Page 47: ...unding cable PE connection Carefully separate this cable You now have the opened Sunny Boy in front of you and can see the position of components and clamps relevant for you You will find The internal fuse The thermally monitored varistors The control system board with the socket for the piggy back board for the com munication The adapter block and the jumpers to set up the input voltage range ...

Page 48: ...laced correctly When screwing the inner screws make sure that the thread in the Sunny Boy case is not damaged by tilted screws Under certain conditions the protection class IP65 cannot be guaranteed any more When mounting the Sunny Boy outside moisture can get into the device and damage the electronics 2 Connect the PV panel by plugging on the MC plug connectors see also chapter 3 3 2 3 Connect th...

Page 49: ...ioned anywhere within the in house net work as they acquire data directly from the AC circuit For trouble free operation the Sunny Boys and the PC socket modem or the Sunny Boy Control must be connected to the same phase of the in house network If the communicating partners are connected to different phases the communication must be established with a so called phase coupling device The phase coup...

Page 50: ...are equipped with a 25 pole COM interface Then a small adapter is necessary order no 39 5010 The visualisation software Sunny Data must be installed How to install Powerline Communication Powerline Communication with a PC The RS232 connector from the SWR COM is plugged into a free COM port of the PC The SWR COM is plugged into the electricity socket For details on the visualisation software Sunny ...

Page 51: ...ssible Communication between the Sunny Boys and the Sunny Boy Control or the PC can then be done with a separate data cable RS232 communication If only one Sunny Boy has to be connected to the PC the easiest way is direct cou pling via an RS232 port A maximum of 15 m is permissible between the PC and the Sunny Boy Single Sunny Boy PC RS 232 Electricity Grid Fig 6 2 Example for RS232 communication ...

Page 52: ...e resistors Fig 6 3 on the system control board are removed Some PCs are equipped with a 25 pin COM port In this case a small adapter is necessary order no 39 5010 Installation Please read chapter 6 3 carefully Connect RS232 connection cable LIYCY 0 25 mm2 minimum three cable with common shield and a maximum length of 15 m You can see the connector lay out in Fig 6 3 The shielding should be connec...

Page 53: ...ld Piggy Back socket Jumpers not mounted PC with DB9 plug in COM1 COM4 PC with DB25 plug in COM1 COM4 DB25 socket DB9 socket Shield connect shield to case light blue resistors removed PC PC or GND TXD RXD GND RXD TXD 232 PB G3 Fig 6 3 System control board Sunny Boy with RS232 cabling ...

Page 54: ...cted to a PC or the Sunny Boy Control via RS485 and a separate data cable Data cables of up to 1200 m are permissible Sunny Boy Sunny Boy Sunny Boy RS485 interface converter Sunny Boy Control PC RS232 RS485 Sunny Boy Sunny Boy Sunny Boy Fig 6 4 Schematic layout of RS485 data transmission with several Sunny Boys Fig 6 5 Cross section of the recommended RS485 cable ...

Page 55: ...propriate cable glands for all Sunny Boys The light blue resistors Fig 6 6 on the system control board are removed If connected to a PC The interface converter RSU485 ordering no 39 0020 is available Sunny Data visualization software is installed on the PC Some PCs have a 25 pole COM port In this case a small adapter ordering no 39 5010 may be necessary ...

Page 56: ...st be removed 2 Sunny Boy nd last Sunny Boy Sunny Boy Control Plug in DB9 PC with interface converter Socket DB9 1 Sunny Boy rst RS485 RS232 Interface converter SUB D 9 pin to SUB D 25 pin No 39 0020 PC with DB 25 Plug in COM1 or COM2 or 680 7 680 connect shield to case PE Jumpers mounted not Jumpers mounted not Jumper 1 mounted connect shield to case PE connect shield to case PE Sunny Boy Control...

Page 57: ...on at the beginning of the cable that is connected to the Sunny Boy Control or the PC One is soldered from pin 3 to pin 6 the other is soldered from pin 5 to pin 8 see Fig 6 6 These resistors are not required for communication with the Sunny Boy Con trol if the corresponding jumpers were plugged on The recommended cable for the RS485 connection is a LIYCY 2 x 0 25 mm twisted pair cable It consists...

Page 58: ...adapter DB9 DB25 Description 1 2 3 4 5 6 7 8 9 8 3 2 20 7 6 4 5 22 DCD Data Carrier Detect RX Receive Data TX Transmit Data DTR Data Terminal Ready GND Signal Ground DSR Data Set Ready RTS Request To Send CTS Clear To Send RI Ring Indicator Table 6 1 Pin designation of the DB9 DB25 adapter ...

Page 59: ...ric Connection 4 Commissioning 5 1 Opening and closing of the Sunny Boy in the Sunny Boy manual The Sunny Boy works with high voltages externally and internally which can cause considerable harm to people Only a qualified elec trician may work on the device especially open it While upgrading the Sunny Boy interface the operator can get into touch both with electronic components and components carr...

Page 60: ...n RS232 or RS485 board Remove the resistors Fig 6 6 on the system control board by cutting them out with a wire cutter Only for installation of a board for Powerline Communication Please make sure that the resistors Fig 6 6 are plugged onto the system control board If not resistors corresponding to 0 Ohm resistors have to be installed in there Plug the desired piggy back module onto the required s...

Page 61: ...able gland Connect the terminal cables to the terminal strip of the system control board and check whether they are firmly fastened Fasten the cable seal of the PG16 cable gland If you have installed RS232 cabling please close the opening in the bottom with the seal included in the packing list Close the device as described in chapter 5 1 ...

Page 62: ...ace with all positive features known under Windows The available measurement channels of the Sunny Boy see chapter 6 5 can be dis played online The data can be displayed manually or automatically The data is stored in files on any available storage medium Special functions allow the installer to modify the operating parameters of the Sunny Boy in order to improve system per formance Please see the...

Page 63: ...sioning of the PV plant Additional features are remote diagnosis via modem and fax messages For global visualization of PV plant data SMA offers the Sunny Data Control PC soft ware under Windows E g the power output of the entire large scale PV plant can be shown in a matrix For the numerous possibilities of establishing a monitoring concept with Sunny Boy Control please see the Sunny Boy Control ...

Page 64: ... are used BFR Betriebsführungsrechner Sequential Control System SRR Stromregelungsrechner Current Control System Measuring Channels Upv Ist PV input voltage Upv Soll PV desired voltage of the internal Upv control Iac Ist current to the grid Uac grid voltage Fac grid frequency Pac power fed to grid Zac grid impedance Riso isolation resistance Ipv current from PV panels E Total energy yield h Total ...

Page 65: ... out of tolerable range F Fac Srr SSR frequency measurement value out of tolerable range F dZac Bfr BFR sudden change of impedance value out of tolerable range F dZac Srr SSR sudden change of impedance value out of tolerable range F Imax internal overcurrent F NUW UAC different values between BFR and SRR for grid voltage F NUW FAC different values between BFR and SRR for grid frequency F NUW Mess ...

Page 66: ...pvMax PV input voltage above the tolerable maximum value F Zac Bfr BFR grid impedance measurement value out of tolerable range F Zac Srr SSR grid impedance measurement value out of tolerable range F Watchdog Watchdog for operation control triggered F ROM Failure during ROM test ...

Page 67: ...ambient temperature ϑU of 25 C Other temperatures must be evaluated with respect to the inaccuracy resulting from these different temperatures Unit Range Resolution Maximal failure Display Measurement ϑU 25 C Input voltage UPV V 0 320 V 1 V 0 55 V 2 Input current IPV mA 0 10000 mA 1 mA 10 mA 4 Grid voltage UAC V 190 300 V 1 V 0 3 V 1 Grid current IAC mA 0 6000 mA 1 mA 12 mA 2 Grid frequency fAC Hz...

Page 68: ...tion behavior the disconnection devices and a long term heavy duty tests We recommend to conduct the following steps in case your PV plant does not oper ate correctly Check the blink code on the lid of the Sunny Boy and compare the code with the blink codes listed in chapter 5 Follow the countermeasures listed there if necessary contact the installer Check the Status and Failure messages in one of...

Page 69: ...de see chapter 5 If Sunny Boy Control or a PC with Sunny Data is present Which status and failure are indicated Can you reproduce the failure How can you reproduce it Does the failure occur sporadically Has this failure always occurred What were the ambient conditions when the failure occurred Information concerning the PV modules Supplier type of modules Number of modules in string Output power O...

Page 70: ...ation of the original warranty period for the delivered item Evidence SMA will only render warranty services when the rejected device is sent back to SMA together with a copy of the invoice the distributor has issued for the consumer The type plate at the device must be fully legible In case of non fulfillment SMA reserves the right to refuse warranty services Conditions SMA will decide whether it...

Page 71: ...the neighborhood of irregular consumers unshielded motors switching power supplies converters etc Furthermore the simultaneous operation of babyphones may lead to short time data transmission disturbances or interrup tions In case of disturbed data transmission via mains lead we alternatively offer communication via separate data line RS232 or RS485 see chapter 6 We do not guarantee that the softw...

Page 72: ...ends on its cell temperature as well as solar radiation The maximum open circuit voltage of the PV panel is reached at the lowest cell temperature Therefore when planning a PV plant take into account the lowest possible ambient temperature of the PV panel Based on this temperature the maximum open circuit voltage of the PV panel can be calculated if the type of PV module is known You can enter the...

Page 73: ... more Therefore the Sunny Boy has got a flexible MPP voltage range There is a fixed ratio of the minimum MPP voltage VMPPmin from the Sunny Boy to the PV panel and the grid voltage VAC as shown in Fig 9 1 The minimum DC voltage is determined according to the current grid voltage The flexible MPP voltage range allows for optimum utilization of the inverter s characteristics and a higher power yield...

Page 74: ...76 According to Fig 9 1 a grid voltage of VAC 230 V results in a minimum MPP voltage of VMPPmin 116 V in the input voltage range At 70 C the MPP voltage of the connected strings may not fall below the respective input voltage range VMPP 70 C min input voltage range Max input open circuit voltage VPV 0 250 V DC Input voltage MPP range VPV 116 V 250 V DC 700 W PACnom 93 V 200 V DC 600 WPACnom 70 V 1...

Page 75: ...current supplied by the connected PV panel exceeds the maximum that can be used How ever the input voltage has to be within the admissible input voltage range All pole disconnection on DC side MC plug connector Over voltage protection thermally monitored varistors Voltage ripple Upp 10 Personnel protection earth fault monitoring Riso 1 MΩ Pole confusion prevention short circuit diode ...

Page 76: ...e UAC 198 251 V AC Output range grid frequency fAC 49 8 50 2 Hz All pole disconnection grid side Mains monitoring with allocated switching devices MSD double Phase shift angle based on fundamental current ϕ 0 Testing voltage 50 Hz 1 2 kV 1 5 s piece type testing Surge voltage test 1 2 50 µs 4 kV serial interface 6 kV External interfaces Data transmission via Powerline Optional Data transmission vi...

Page 77: ...cal Description SB700 11 EE 77 SMA Regelsysteme GmbH 100 100 0 10 70 80 60 90 50 80 90 10 40 70 30 30 40 50 20 20 60 0 Fig 9 3 Sunny Boy 700 efficiency Pac Pacnom Fig 9 4 Output current and output voltage of the Sunny Boy ...

Page 78: ...N EN 60555 part 2 Grid monitoring Mains monitoring with allocated switching devices M in accordance with VDEW E DIN VDE 0126 11 94 Low voltage regulation DIN EN 50178 4 98 VDE 0160 DIN EN 60146 part 1 1 3 94 VDE 0558 part 11 Device Protection Protection in accordance with DIN EN 60529 IP65 Weight and Dimensions Dimensions w x h x d approx 322 x 290 x 180 mm Weight approx 16 kg Ambient Conditions f...

Page 79: ...taller Usoll Konst V 125 0 250 0 140 0 Installer 100 0 140 75 0 140 I NiTest mA 0 6000 4500 4000 3000 Installer Uac Min V 180 300 198 198 198 Installer Uac Max V 180 300 251 251 251 Installer Fac Min Hz 49 51 49 81 49 81 49 81 Installer Fac Max Hz 49 51 50 19 50 19 50 19 Installer Zac Max mOhm 0 20000 1700 1700 1700 Installer dZac mOhm 0 2000 350 350 350 Installer Hardware BFS Ver sion Fixed Softw...

Page 80: ...0 Technical Description SB700 11 EE 80 SMA Regelsysteme GmbH 10 Appendix Certificates for the Sunny Boy 700 SMA Declaration of Conformity for the Sunny Boy 700 Clean Report of Findings for MSD in the Sunny Boy 700 ...

Page 81: ...Sunny Boy 700 Technical Description SB700 11 EE 81 SMA Regelsysteme GmbH ...

Page 82: ...Sunny Boy 700 Technical Description SB700 11 EE 82 SMA Regelsysteme GmbH ...

Page 83: ...y 2000 Technical Description Sunny Boy 2500 Technical Description Sunny Boy 3000 User Manual Sunny Data User Manual Sunny Data Control User Manual Sunny Boy Control User Manual SWR COM Socket Powerline Modem Sunny Boy Info periodical newsletter with up to date information on the Sunny Boy SMA CD products technical documentation driver Manual Improved Powerline Communication with the Sunny Boy Fami...

Page 84: ...atest information concerning the Sunny Boy inverter family The newest Sunny Data software for downloading You can leave messages for SMA This is especially useful if you want to send data recorded from your PV plant to the Sunny Boy service Those who want to know more about SMA Regelsysteme GmbH and its products are very welcome to visit us on our homepage ...

Page 85: ...GmbH Address SMA Regelsysteme GmbH Hannoversche Straße 1 5 D 34266 Niestetal Telephone 0561 9522 0 operator 0561 9522 499 Sunny Boy Service Fax 0561 9522 100 main fax 0561 9522 4699 Sunny Boy Service eMail info sma de Internet http www sma de Appendix drilling template ...