DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
95
Model
Power
Supply
Capability of
Air Switch(A)
(Outdoor
/Indoor)
Minimum
Sectional Area of
Earth Wire(mm
2
)
(Outdoor /Indoor)
Minimum
Sectional Area of
Power Supply
Wire(mm
2
)
(Outdoor /Indoor)
ASGE-
18
AI
/
ASC-
18AI
2
0/6 2.5/1.0 2.5/1.0
ASGE-
24
AI
/
ASC-
24AI
2
0/10 2.5/1.5 2.5/1.5
ASGE-
24
AI S
/
ASC-
24AI
S
2
0/10 2.5/1.5 2.5/1.5
ASGE-
36
AI
/
ASC-
36AI
2/10 6.0/1.5 6.0/1.5
ASGE-
36
AI S
/
ASC-
36AI
2/10 6.0/1.5 6.0/1.5
ASGE-
42
AI-3 S
/
ASC-
42
AI S
2/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-
36
AI-3
/
ASC-
36AI
2
5/10 4.0/1.5 4.0/1.5
ASGE-
36
AI-3 S/ ASC-
36
AI 2
5/10 4.0/1.5 4.0/1.5
ASGE-
42
AI-3
/
ASC-
42AI
2
5/10 4.0/1.5 4.0/1.5
380-415V~
3 Ph
50HZ
Note
:
The specification of power cord mentioned hereby is defined as the required specification when
wiring with BV single core cable (2 ~ 4 pieces) under the cover of PVC pipe, and environment
temperature shall be at 40 ; Air switch shall be selected accordi
℃
ng to 40 temperature condition,
℃
and shall in “D” type. if the installation condition on site changed, please consider the modification
on the required specification of Power cord and Air switch, according to the specification manual
provided by manufacture.
Determine the wire size for indoor unit according to the number of connected indoor units
downstream.
Observe local regulation regarding wire size selection and installation.
Caution:
Keeps the refrigerant piping system and the indoor-indoor / indoor-outdoor control wiring systems
together.
When running power wires and control wires parallel to each other, either run them through
separate conduits, or maintain a suitable distance between them. (Current capacity of power wires:
10A or less for 300m,50A or less for 500m)
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...