DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
120
◆
Radiator overheat protection
Monitor display
Mainboard indicator
Radiator overheat
protection
Blink Blink Blink
Bright Blink
Bright
If the outdoor
unit is in good
radiation?
If the air outlet and return
air inlet of the outdoor unit
is short circuited, it will
cause the radiating effect to
become poor.
If the radiator
is dirty or
blocked?
If the radiator is dirty or
blocked, it will cause the
radiating effect to become
poor.
If IPM module is
well tightened?
If IPM module is not
tightened, it will cause the
module temperature to
become too high, or even
burn the module.
If the silicate gel
on IPM module is
uniformly coated?
If the coating of silicate gel is not
uniform, it will cause poor radiation to
the module, or uneven distribution of
the temperature, or even burn the
module as the sensor cannot detect
the temperature in some area is too
high.
If the silicate gel
coated on IPM
module can meet
the requirements?
If the coating of silicate
gel is too thick, it will also
affect the radiating effect
or even burn the module.
Please check if the
sensor is failed, or
reinstall the module and
tighten it.
Record and feed back
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...