DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
119
Abnormal noise from PFC inductor
◆
Abnormal noise
from PFC
inductor
Abnormal
noise is heard
when the
compressor is
started
Dry the PFC board
and clear off the dirt
or eliminate the
short-circuit point.
Reinstall and start the
machine for testing.
Work normally?
Cut off the power
for 1 minute or
reduce the busbar
voltage to 36V or
lower. Then, check
the PFC board.
If it is moistened,
dirty or short
circuited?
Check the
operating
conditions of
compressor
1. If it is moistened, find out the cause and take
proper measures to prevent moisture. Dry the
PFV board and apply moisture-proof glue.
2. If it is dirty, find out the cause and take
dustproof measures. If the air quality of service
environment is poor, it is also required to clear
off the dirt periodically.
3. If it is short circuit, find out the cause and
clean the electric box to prevent the iron scraps
or other conductive substances from attaching
on the board.
Does the
compressor
vibrate heavily or
give out
abnormal noise?
Driver board is
damaged. Please
replace the driver
board.
PFC board is damaged.
Please replace the PFC
board.
Record and feed back
No
Yes
Yes
Yes
Yes
No
No
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...