DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
161
Removal and Installation of Oil-Liquid Separator
Remarks: Before removing the oil-liquid separator, make sure that there is no refrigerant
inside the pipe system and that the power has been cut off.
1. Remove the
screws fixing the
oil-liquid
separator
●
Firstly, cut off the power.
●
Recycle the refrigerant
properly.
●
Use screwdriver to loosen
the screws fixing the oil-liquid
separator.
2. Remove the
fixing clamp of
oil-liquid
separator
●
Remove the oil-liquid
separator fixing clamp from
the support.
3. Remove the
inlet and outlet
connection pipes
of oil-liquid
separator
●
Use gas welding to heat the
inlet and outlet connection
pipes on oil-liquid separator.
Then, pull them out from the
oil-liquid separator.
●
Weld by charging nitrogen
for protection, with the
nitrogen pressure kept at
0.5±0.1kgf/c
㎡
(relative
pressure).
●
During heating, take care
to prevent the substances
around from burn due to high
temperature.
Remove the inlet and
outlet connection
pipes of oil-liquid
separator
Remove the screws
fixing the oil-liquid
separator
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...