DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-3-7
2
)
Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints
to ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing
before decorating the ceiling.
3
)
Matters of Attention
The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter
of polythene pipe: Outer diameter 25mm Surface thickness
≥
1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of
air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m. (As
shown in Figure 1-3-8)
1-1.5m
○
(Correct) 1/100 or more gradient
×
(wrong)
Figure 1-3-8
The install height of the drain raising pipe should less than 280mm.
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond
300mm. (As shown in Figure 1-3-9)
Celling
1-1.5m
Hanger bracket
Below
1120mm
Above
280mm
200mm
Drainage raising pipe
Drainage hose
(attachment)
Cassette type unit
with in 300mm
Clamp(attachment)
Figure 1-3-9
The slant gradient of the attached drain hose should be within 75mm so that the drain
hole
doesn’t
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...