DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
121
Tripping
◆
Tripping
If the switching
capacity can meet
the requirements?
Tripped once
energized
Tripped when
the compressor
is started?
Install the electric
switch according to the
capacity requirements
as specified in
operating instructions.
Check PFC board. Cut off the
power for 1 minute or reduce
the busbar voltage to 36V or
lower. Then, remove the
connection cable on PFC board
and use multimeter to measure
if P-N, or P-L1_2, or L1_2-N on
PFC board is short circuited.
Leakage current
is too high.
Please check for
moisture, or
replace the filter.
Short circuited?
The PFC module is damaged.
Replace the PFC module and check
if AC contactor is stuck. Meanwhile,
ensure that P-N is short circuited.
The possible reasons causing this
trouble include:
①
The screws fixing
the module are not correctly
tightened;
②
The AC contactor on
AC side in parallel to the recharging
resistor is stuck, and the transient
recharging current upon
energization is too high;
③
The input
voltage is too low; or
④
The cable
connection is wrong.
Check driver board. Cut off the
power for 1 minute or reduce
the busbar voltage to 36V or
lower. Then, remove the
connection cable on driver
board and use multimeter to
measure if P-N, or P-U, or P-V,
or P-W, or U-N, or V-N, or W-N
on driver board is short
circuited.
Short circuited?
If the front-end
AC contactor is
stuck?
If the insulation
on PFC inductor
winding is
damaged?
The system is
abnormal. Please check
the compressor
connections or winding
for short circuiting or
other troubles.
The AC contactor
is damaged.
Please replace
with a same type
of contactor.
Replace PFC
inductor
Check if the
cable
connection is
wrong
Record and
feed back
Leakage current
is too high.
Please check for
moisture, or
replace the filter.
PFC ON?
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
No
No
No
The IPM module is damaged.
Replace the driver board. The
possible reasons causing this
trouble include:
①
The screws
fixing the module are not
correctly tightened;
②
The
load is severely overloaded; or
③
The interference causes
short circuiting inside IPM
module.
No
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...