![Sinclair ASC-18A Service Manual Download Page 13](http://html.mh-extra.com/html/sinclair/asc-18a/asc-18a_service-manual_1280114013.webp)
4.1.2 Ceiling Type
Indoor unit
ASF-
18AI
Models
Outdoor unit
ASGE-
18
AI
kW
5.0
Cooling
Btu/h
1700
kW
5.8
Nominal
Capacity
Heating
Btu/h
19800
Cooling kW
1.81
Power
Input
Heating k
W
1.94
EER/COP W/W
2.76
/
2.99
Indoor Unit
ASF-
18AI
Power Supply
-
220-240V~
/
1 Ph
/
50HZ
Heat Exchange
-
Cross Fin Coil
Type
-
Centrifugal fan
Drive
-
Direct Driver
Motor Output
kW
0.04
Fan
Air Flow
m3/h
700
Sound Pressure Level(H/M/L)
dB(A)
54/50/46
Air Filter
-
Standard washable synthetic
Drain Piping
mm
φ
28×1.5
Dimensions (W×H×D)
(Outline/Package)
mm
836×238×695
/935×295×805
Weight(Net/Gross)
kg 26/33
Outdoor Unit
ASGE-
18A
I
Power Supply
-
220-240V~/1 Ph/50HZ
Heat Exchange
-
Cross Fin Coil
Type
―
Axial
fan
Motor Output
kW
0.03
Fan
Fan Motor Speed
rpm
850
Type
-
ROTARY
Compressor
Power Input
W
1630
Type
-
R410A
Control
-
Electronic Expansion Valve
Refrigerant
Charge kg
1.50
Dimensions (W×H×D)
(Outline/Package)
mm
820×540×320
/870×360×590
Weight(Net/Gross) kg 36/40
Liquid mm
6.35
Gas mm 12.70
Max. Length
m
20
Piping
Connections
Max. Height Difference
m
15
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...