DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
153
4. Assemble the new
electronic expansion valve
●
Assemble the new
electronic expansion valve
to correct position.
●
During welding, use wet
cloth to wrap the electronic
expansion valve body.
●
Weld by charging nitrogen,
with the nitrogen pressure
kept at 0.5±0.1kgf/c
㎡
(relative pressure).
5. Assemble the coil of
electronic expansion valve
●
After welding of the
connection pipe, mount the
coil according to
disassembly procedures.
●
Carry out leakage
detection to the system. If no
problem, establish vacuum
and charge refrigerant
through process pipe.
Disassembly and Assembly of electrical parts box
Remark : Before removing the electric box or electric box sub-assembly, make sure that the
power has been cut off.
Step Illustration
Handling
Instruction
1. Remove the electric box
cover
●
Cut off the power.
●
Use the screwdriver to
remove the fixing screws
between electric box cover
and electric box.
●
Remove the cover from
electric box.
2. Remove the power cables
of motor and other
components
●
Remove the cables
connecting the electric
elements in the electric box
to the external elements
(e.g. the power cables of
compressor and motor)
Note: When removing the
connection, make sure to
Summary of Contents for ASC-18A
Page 2: ...last actualization 2011 ...
Page 27: ...CONTROL ...
Page 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Page 52: ...INSTALLATION ...
Page 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Page 102: ...96 MAINTENANCE ...
Page 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Page 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Page 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Page 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Page 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Page 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Page 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Page 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Page 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Page 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Page 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Page 219: ......
Page 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Page 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Page 228: ...Model ASGE 36AI ...
Page 231: ...Model ASGE 36AI S ...
Page 236: ...Model ASGE 36AI 3 S ...
Page 238: ...Model ASGE 42AI 3 ...
Page 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Page 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Page 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Page 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...