PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
198
Manual, 03/2017, NEB535219502000/RS-AB/008
ID No.
Byte
Bit
Alarm bit
Error
No.
*)
Meaning/acknowledgment
366
8
2
Parameters cannot be changed in ON state
-
Attempted parameter change while
motor is running or during relevant
device function, which has caused
the trip.
Alarm bit is always deleted when
acknowledged with "Trip Reset" or
valid parameters have been
received.
368
8
3
Parameters disabled CPU/master active
-
Alarm bit is updated continually, soft
starter ignores parameters from the
PLC.
8
4-7
Reserved = 0
-
Device functions
9
0-2
Reserved = 0
-
369
9
3
Factory settings restored
-
Alarm bit is always deleted when
acknowledged with "trip reset".
9
4-7
Reserved = 0
-
367
10
Incorrect parameter number (low byte)
-
In conjunction with bytes 81 and 82,
specifies the ID No. of the first
parameter not accepted.
Alarm bit is always deleted when
acknowledged with "trip reset".
11
Incorrect parameter number (high byte)
-
12
0-1
Reserved = 0
-
1421
12
2
Impermissible I
e
/CLASS setting
-
12
3-7
Reserved = 0
-
1449
13
0
Parameter set 1 active
-
1450
13
1
Parameter set 2 active
-
1451
13
2
Parameter set 3 active
-
13
3
Reserved = 0
-
1453
13
4
Parameter set change impermissible
-
13
5-7
Reserved = 0
-
14
0-1
Reserved = 0
-
1404
14
2
Motor heating active
-
1402
14
3
DC braking active
-
1403
14
4
Dynamic DC braking active
-
1471
14
5
Star/delta motor connection
-
1472
14
6
Inside-delta motor connection
-
1473
14
7
Motor connection type unknown
-
1408
15
0
No load
-
15
1
Reserved = 0
-
1409
15
2
Phase failure L1
-
1410
15
3
Phase failure L2
-
1411
15
4
Phase failure L3
-
1412
15
5
Rotational direction of line frequency right
-