PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
211
ID No. Byte
Bit
Meaning
Only in
data set
131
Value range/[coding]
Factor
163
96
Output 1 - action
X
•
No action (default) [0]
•
Control source PIO DO 1.0 output 1 [1]
•
Control source PAA-DO 1.1 output 2
[2]
•
Control source input 1 [6]
•
Control source input 2 [7]
•
Control source input 3 [8]
•
Control source input 4 [9]
•
Run-up [10]
•
Operation/bypass [11]
•
Coasting down [12]
•
ON time motor [13]
•
Control command motor ON [14]
•
Fan [15]
•
DC brake contactor [16]
•
Device ON [18]
•
Group warning [31]
•
Group fault [32]
•
Bus fault [33]
•
Device fault [34]
•
Ready to start ON for motor [38]
164
97
Output 2 - action (see Output 1 -
action)
X
165
98
Output 3 - action (see Output 1 -
action)
X
166
99
Output 4 - action
100...111 Reserved = 0
116
112
Breakaway time
0 ... 2 s [0 ... 200]
0.01 s
117
113
Breakaway voltage
40 ... 100 % [8 ... 20]
5 %
169
114...115 Maximum starting time
0 ... 1 000 s [0 ... 10 000]
0.1 s
170
116...117 Starting time
0 ... 360 s [0 ... 3 600]
0.1 s
171
118...119 Coast-down time
0 ... 360 s [0 ... 3 600]
0.1 s
172
120
Starting torque
10 ... 100 % [2 ... 20]
5 %
118
121
Limiting torque
20 ... 200 % [4 ... 40]
5 %
173
122
Stopping torque
10 ... 100 % [2 ... 20]
5 %
123
Reserved = 0
124
Reserved = 0
119
125
Motor thermal capacity
1 ... 100 % [1 ... 100]
1 %
126...129 Reserved = 0
178
130
Dynamic braking torque
20 ... 100 % [4 ... 20]
5 %