PROFIBUS DP communication module
9.6 PROFIBUS DP commissioning using the GSD file in STEP 7 (example)
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
167
The following table shows which parameters are mutually dependent and how they must be
set:
Table 9- 4
Interdependent parameter settings
Parameters
Settings
Rated operational current I
e
Depends on
Tripping class CLASS (refer to chapter Technical
data of the power unit (Page 259))
Upper current limit
Greater than
Lower current limit, chapter Specifying current limit
Maximum starting time
Greater than
Starting time, chapter Specifying the startup mode
(Page 63)
Limiting torque
Greater than
Starting torque, chapter Specifying the startup
mode (Page 63), torque control and torque control
with current limiting.