PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
196
Manual, 03/2017, NEB535219502000/RS-AB/008
ID No.
Byte
Bit
Alarm bit
Error
No.
*)
Meaning/acknowledgment
341
4
1
Asymmetry tripping
F24
Tripping of the motor due to
asymmetry.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
334
4
2
I
e
limit value overshot
F7
Limit exceeded, alarm bit is updated
continually.
335
4
3
I
e
limit value undershot
F8
Limit undershot, alarm bit is
updated continually.
336
4
4
I
e
current limit tripping
F24
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
4
5
Reserved = 0
-
4
6
Reserved = 0
-
339
4
7
Motor stalled - switched off
F24
Trip, stalling current detected for
longer than the permitted stalling
time.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
344
5
0
Input 1
-
States of the inputs
"1" = active, HIGH level is present
"0" = inactive, LOW level is present
Alarm bit is updated continually.
345
5
1
Input 2
-
346
5
2
Input 3
-
347
5
3
Input 4
-
5
4-7
Reserved = 0
-
342
6
0
Ground fault detected
-
Ground fault is present, alarm bit is
updated continually.
343
6
1
Ground fault tripping
F24
Tripping of the motor due to ground
fault.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
353
6
2
Quick stop active
F26, F24 Tripping of the motor due to quick
stop.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
6
3
Reserved = 0
-