PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
195
ID No.
Byte
Bit
Alarm bit
Error
No.
*)
Meaning/acknowledgment
302
0
6
Group fault
-
At least 1 error that generates an E
No. is set.
Alarm bit is deleted when the cause
of tripping has been eliminated and
acknowledged with "trip reset, auto
reset, OFF command"
304
0
7
Group warning
-
At least 1 warning is pending, alarm
bit is updated continually.
1
0
Reserved = 0
-
319
1
1
No supply voltage
F17, F24 Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
1
2
Reserved = 0
-
312
1
3
Starting active
-
Alarm bit is updated continually.
313
1
4
Coast down active
-
1
5
Reserved = 0
-
316
1
6
Electrical braking active
-
Brake output is switched on by the
soft starter, alarm bit is updated
continually.
314
1
7
Slow speed active
-
Alarm bit is updated continually.
Protective function: Motor/cable/ short-circuit
324
2
0
Temperature sensor overload
F4
Overload detected, alarm bit is
updated continually.
325
2
1
Temperature sensor wire break
F6
Thermistor circuit interrupted, alarm
bit is updated continually.
326
2
2
Temperature sensor short-circuit
F1
Short-circuit in thermistor circuit,
alarm bit is updated continually.
327
2
3
Thermal motor model overload
F4
Overload detected, alarm bit is
updated continually.
328
2
4
Overload tripping
F24
Motor is tripped due to a detected
overload.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset"/"auto reset".
329
2
5
Idle time active
-
Alarm bit is updated continually.
330
2
6
Cooling time active
-
Alarm bit is updated continually.
2
7
Reserved = 0
-
3
0-6
Reserved = 0
-
352
3
7
Input control
-
Device receives control commands
via the inputs, alarm bit is updated
continually.
340
4
0
Asymmetry detected
-
Asymmetry is present, alarm bit is
updated continually.