General technical data
11.3 Technical data
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
255
Table 11- 3 Normal starting (CLASS 10) in inline circuit - Part 3/3
Ambient temperature 40
℃
Ambient temperature 50
℃
Rated
operation-
al voltage
U
e
Rated
opera-
tional
current
I
e
Rated power of three-phase
motors at rated operational
voltage U
e
Rated
opera-
tional
current
I
e
Rated power of three-phase
motors at rated operational
voltage U
e
Article No.
V
A
230 V
kW
400 V
kW
500 V
kW
690 V
kW
A
200 V
HP
230 V
HP
460 V
HP
575 V
HP
400 ... 690 113
-
55
75
110
100
-
-
75
75
3RW44 34-x
1
BCx
2
6
134
-
75
90
132
117
-
-
75
100
3RW44 35-x
1
BCx
2
6
162
-
90
110
160
145
-
-
100
125
3RW44 36-x
1
BCx
2
6
203
-
110
132
200
180
-
-
125
150
3RW44 43-x
1
BCx
2
6
250
-
132
160
250
215
-
-
150
200
3RW44 44-x
1
BCx
2
6
313
-
160
200
315
280
-
-
200
250
3RW44 45-x
1
BCx
2
6
356
-
200
250
355
315
-
-
250
300
3RW44 46-x
1
BCx
2
6
432
-
250
315
400
385
-
-
300
400
3RW44 47-x
1
BCx
2
6
551
-
315
355
560
494
-
-
400
500
3RW44 53-x
1
BCx
2
6
615
-
355
400
630
551
-
-
450
600
3RW44 54-x
1
BCx
2
6
693
-
400
500
710
615
-
-
500
700
3RW44 55-x
1
BCx
2
6
780
-
450
560
800
693
-
-
600
750
3RW44 56-x
1
BCx
2
6
880
-
500
630
900
780
-
-
700
850
3RW44 57-x
1
BCx
2
6
970
-
560
710
1000 850
-
-
750
900
3RW44 58-x
1
BCx
2
6
1076
-
630
800
1100 970
-
-
850
1100 3RW44 65-x
1
BCx
2
6
1214
-
710
900
1200 1076
-
-
950
1200 3RW44 66-x
1
BCx
2
6
x
1
2 = screw-type terminals, 6 = spring-loaded terminals
x
2
3 = 115 V AC, 4 = 230 V AC