PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
204
Manual, 03/2017, NEB535219502000/RS-AB/008
9.12.13
Data set 96 - Reading the maximum pointer
Table 9- 27 Data set 96 - Reading the maximum pointer
ID No. Byte
Bit
Meaning
Value range/[coding]
Increment Note
Maximum pointer
656
4
Phase current I
L1 min
(%)
0 ... 797 % / [0 ... 255]
3.125%
In bypass
operation
657
5
Phase current I
L2 min
(%)
0 ... 797 % / [0 ... 255]
3.125%
658
6
Phase current I
L3 min
(%)
0 ... 797 % / [0 ... 255]
3.125%
7
Reserved = 0
653
8
Phase current I
L1 max
(%)
0 ... 797 % / [0 ... 255]
3.125%
654
9
Phase current I
L2 max
(%)
0 ... 797 % / [0 ... 255]
3.125%
655
10
Phase current I
L3 max
(%)
0 ... 797 % / [0 ... 255]
3.125%
11
Reserved = 0
652
12
Maximum tripping current I
A max
(%)
0 ... 1000 % / [0 ... 320]
3.125%
Current during
switch-off due to
error
651
14
Number of motor overload trips
0 ... 65 535 / [0 ... 65 535]
1
Motor protection,
temperature
sensor, stalling
659
16
Maximum tripping current I
A max
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
Current during
switch-off due to
error
660
20
Phase current I
L1 min
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
In bypass
operation
661
24
Phase current I
L2 min
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
662
28
Phase current I
L3 min
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
663
32
Phase current I
L1 max
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
664
36
Phase current I
L2 max
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
665
40
Phase current I
L3 max
(rms)
0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
666
44
Line-to-line voltage U
L1 - L2min
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
Reset to 0 in the
event of phase
failure or switch-
off of main
voltage.
667
46
Line-to-line voltage U
L2 - L3min
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
668
48
Line-to-line voltage U
L3 - L1min
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
669
50
Line-to-line voltage U
L1 - L2max
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
670
52
Line-to-line voltage U
L2 - L3max
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
671
54
Line-to-line voltage U
L3 - L1max
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
672
56
Electronics supply voltage U
NS min
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
Reset to zero at
"Power on"
673
58
Electronics supply voltage U
NS max
(rms)
0 ... 1500 V / [0 ... 15 000]
0.1 V
674
60
Maximum heatsink temperature
1 ... -40 °C/ [-40 ... 127]
1 °C
675
61
Maximum contact block heating
0 ... 250 % / [0 ... 250]
1 %