EMC Immunity
The SINAMICS G110M drives have been tested in accordance with the immunity requirements
of category C3 (industrial) environment:
Table A-12
EMC Immunity
EMC Phenomenon
Standard
Level
Performance
Criterion
Electrostatic Discharge (ESD)
EN 61000-4-2
4 kV Contact discharge
A
8 kV Air discharge
Radio-frequency Electromagnet‐
ic Field
EN 61000-4-3
80 MHz … 1000 MHz
10 V/m
A
Amplitude modulated
80 % AM @ 1 kHz
Fast Transient Bursts
EN 61000-4-4
2 kV @ 5 kHz
A
Surge Voltage
EN 61000-4-5
1 kV differential (L-L)
A
1.2/50 μs
2 kV common (L-E)
Conducted
EN 61000-4-6
0.15 MHz … 80 MHz
10 V/rms
A
Radio-frequency Common Mode
80 % AM @ 1 kHz
Mains Interruptions & Voltage
Dips
EN 61000-4-11 95 % dip for 3 ms
A
30 % dip for 10 ms
C
60 % dip for 100 ms
C
95 % dip for 5000 ms
D
Voltage Distortion
EN 61000-2-4
10 % THD
A
Voltage Unbalance
EN 61000-2-4
3 % Negative Phase Sequence
A
Frequency Variation
EN 61000-2-4
Nominal 50 Hz or 60 Hz (± 4 %) A
Commutation Notches
EN 60146-1-1
Depth = 40 %
A
Area = 250 % x degrees
Appendix
A.3 Electromagnetic Compatibility
Distributed converter for SIMOGEAR geared motors
414
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL